{"id":39,"date":"2022-04-27T12:33:43","date_gmt":"2022-04-27T16:33:43","guid":{"rendered":"https:\/\/opentextbc.ca\/plumbing3f\/chapter\/calculating-transmission-loss\/"},"modified":"2022-08-10T16:31:22","modified_gmt":"2022-08-10T20:31:22","slug":"calculating-transmission-loss","status":"publish","type":"chapter","link":"https:\/\/opentextbc.ca\/plumbing3f\/chapter\/calculating-transmission-loss\/","title":{"raw":"Learning Task 4","rendered":"Learning Task 4"},"content":{"raw":"Rooms have ceilings, floors, and walls with doors and windows. Transmission losses must be calculated for each surface that has unconditioned space on the other side of it. This means that a floor with a heated room below it would be considered to not have any downward heat loss. The same is said for a ceiling with a heated room above it or a wall that abuts a heated room. In short, only surfaces that separate a heated space from the outdoors need to have heat losses calculated for them.\n<h1>Transmission Losses through Windows and Doors (Openings)<\/h1>\nThe \u201cU\u201d values used for doors are the same as for windows. A \u201cU\u201d value, based on parameters such as single, double or triple glazed with or without special coatings and fillers, is selected from a table, and multiplied by area in ft\u00b2 and by the DTD. As an example, 48 ft\u00b2 of doors and windows with a \u201cU\u201d value of 0.59 in Penticton would calculate to be 48 \u00d7 0.59 \u00d7 67 = 1,897 BTUH.\n<h1>Walls and Openings<\/h1>\nWalls that separate heated (conditioned) spaces from the outdoors are called \u201cexposed walls\u201d, and they will have an area that includes windows and doors. The losses through windows and doors (\u201copenings\u201d) must be calculated separately, as they will have different \u201cU\u201d factors than will the walls themselves (see above). The easiest way to perform an exposed wall calculation is to do a takeoff of the area of the openings first. If a room has a total of 108 ft\u00b2 of openings in its exposed walls, that area would be subtracted from the total area (length \u00d7 height) of the exposed wall. So, an exposed wall that measures 28 feet long by 8 feet high would have a gross area of 224 ft\u00b2. When the openings are subtracted from that gross area, the net area of exposed wall becomes 224 \u2013 108 = 116 ft\u00b2. The heat loss formulas can now be applied to the net wall area. Table 2 lists the \u201cU\u201d values for framed walls whose exterior finishes are lumped together into one category. In other words, it doesn\u2019t matter what the exterior wall finish is \u2013 the \u201cU\u201d value depends upon the \u201cR\u201d value of the insulation in the wall cavities. So, for our exterior wall in Penticton, with a net area of 116 ft\u00b2, using R20 insulation in the walls, the calculation would be 116 \u00d7 0.05 \u00d7 67 = 389 BTUH\n<h1>Ceiling and Floor Losses<\/h1>\nCeiling losses will only be counted for rooms on a top floor, and are listed as either \u201croof with attic space\u201d (normal residential construction using trusses) or \u201cbuilt up roof, no attic space\u201d (typically flat or vaulted roofs) with an insulation value attached to them. Floor losses (other than basements) will only be counted if they are located over unheated space such as an open carport (\u201cwood over exposed space\u201d) or a garage (\u201cwood over enclosed space\u201d). The insulation values will determine the \u201cU\u201d value chosen from the table, and their transmission losses are calculated in the same manner as with openings and exposed walls.\n<h1>Thermal Bridging<\/h1>\nOur previous example did not make mention at all of a thermal resistance for the 2 \u00d7 6 studs themselves. This is because they are spaced at either 16\u2033 or 24\u2033 centres along the wall and are difficult to allow for. Some heat load designers will include a small allowance for the studs when coming up with the \u201cU\u201d value for an assembly but this is a matter of designer preference.\n\nThe studs that form the support system for walls will have a heat loss through them which is higher than that of the insulation between them. This occurrence is known as \u201cthermal bridging\u201d. By definition, thermal bridging, also known as cold bridging or thermal bypass, is an area or component of an object which has a higher thermal conductivity than the surrounding materials, creating a path of least resistance for heat transfer. Overlooked for a great period of time, thermal bridging has recently come to the forefront of heat load calculations as designers strive to be as accurate and comprehensive as possible in their estimates. Thermal bridging not only causes a loss of heat within the space, it can also cause the warm air inside the space to cool down. When heat attempts to escape a room, it follows the path of least resistance. Likewise, the same process occurs during the summer, only in reverse, allowing heat to enter your otherwise cool building, called heat gain. Thermal bridging happens when a more conductive material allows an easy pathway for heat flow, usually where there is a break in (or penetration of) the insulation. Some common locations include:\n<ul>\n \t<li>The junctions between the wall and the floor, roof, or doors and windows.<\/li>\n \t<li>The junction between the building and the deck or patio<\/li>\n \t<li>Penetrations in the building envelope to include pipes or cables<\/li>\n \t<li>Wood, steel, or concrete envelope components such as foundations, studs, and joists<\/li>\n \t<li>Recessed lighting<\/li>\n \t<li>Window and door frames<\/li>\n \t<li>Areas with gaps in insulation<\/li>\n<\/ul>\nIn short, any area where there isn\u2019t a continuous, unbroken layer of insulative material can be considered a thermal break. These areas should be addressed in both the design and construction phase, as studies have show that in an otherwise airtight and insulated home,\u00a0<a href=\"https:\/\/www.kore-system.com\/blog\/thermal-bridging-what-it-is-and-why-you-should-avoid-it\" target=\"_blank\" rel=\"noopener\">thermal bridges can account for a heat loss of up to 30%<\/a>. Whether you\u2019re building a new home or retrofitting an existing structure, care should be taken to avoid unnecessary breaks or penetrations in the building envelope so that the possibility of thermal bridging decreases.\n<h1>Slab Edge Loss<\/h1>\n[caption id=\"attachment_38\" align=\"aligncenter\" width=\"647\"]<img class=\"size-full wp-image-36\" src=\"https:\/\/opentextbc.ca\/bccantiracistbookclubhub\/wp-content\/uploads\/sites\/405\/2022\/08\/image9.jpeg\" alt=\"\" width=\"647\" height=\"393\"> Figure 1 Slab edge loss[\/caption]\n\nThe thermal bridging that occurs at the point where the indoor concrete slab meets the concrete foundation wall is almost inevitable. Concrete has a low \u201cR\u201d value and there is little that can be done to mitigate the transmission of large amounts of heat between the two masses. Therefore, there will be a category of heat loss called \u201cslab edge loss\u201d that is calculated when using slab-on-grade construction. The formula is written as:\n<p style=\"text-align: center;\">Slab edge length (ft) \u00d7 \u201cU\u201d value \u00d7 \u0394T = BTUH.<\/p>\nThe slab edge \u201cU\u201d factor, from the table above, is either 0.69 when using 1\u201d insulation, or 0.53 when 2\u201d insulation is used.\n\nAs an example, if a room with slab-on-grade construction had 32 lineal feet of exposed slab edge with 2\u201d insulation and the DTD was 67\u00b0F, the calculated slab edge loss would be 32 \u00d7 0.53 \u00d7 67 = 1,136 BTUH. This would be added to the transmission and infiltration losses for that room.\n\nWith radiant floor heating, slab edge insulation is a must. A strip of rigid insulating material such as polystyrene is sandwiched between the two concrete masses to try to reduce the thermal bridging effect. As well, rigid polystyrene (XPS) is commonly attached to the outside of the foundation wall, with a protective sheet of galvanized sheet metal covering it, to further reduce the heat loss through the concrete to the soil and outside air.\n\n[caption id=\"attachment_38\" align=\"aligncenter\" width=\"635\"]<img class=\"wp-image-37 size-full\" src=\"https:\/\/opentextbc.ca\/bccantiracistbookclubhub\/wp-content\/uploads\/sites\/405\/2022\/08\/image10-e1651172470700.jpeg\" alt=\"\" width=\"635\" height=\"519\"> Figure 2 Slab edge insulation[\/caption]\n<h1>Basement Concrete Slab Loss<\/h1>\nIf a basement concrete floor is more than 2 feet below finish grade, a downward loss should be calculated. The formula is similar to that for walls, except that the IDT can be lower if desired. Using 65\u00b0F (18\u00b0C) as an allowable value for an unfinished basement, the calculation would be:\n<p style=\"text-align: center;\">Area (ft\u00b2) \u00d7 DTD (65 \u2212 ODT) \u00d7 0.04 (\u201cslab below grade\u201d from \u201cU\u201d values table above) = BTUH<\/p>\nIf the slab is being heated through radiant means, then the slab temperature is used as the IDT.\n<h1>Infiltration\/Exfiltration Loss<\/h1>\nToday\u2019s structures are far more airtight than were their counterparts of 50 years ago. Old wood frame double-hung, single pane windows have long ago given way to double or triple glazed gas-filled reflective windows mounted in vinyl frames. Caulking, weatherstripping and energy-conserving measures make today\u2019s structures far less drafty than ever before. That said, there are still imperfections in building envelopes that will allow heated interior air to escape to the outdoors, or cold outside air to be forced into the living space. These heat losses, which can be classified as due to convection, are simply referred to as \u201cinfiltration losses\u201d.\n\n[caption id=\"attachment_38\" align=\"aligncenter\" width=\"500\"]<img class=\"wp-image-38 size-full\" src=\"https:\/\/opentextbc.ca\/bccantiracistbookclubhub\/wp-content\/uploads\/sites\/405\/2022\/08\/image11-e1651172574272.jpeg\" alt=\"Heat loss from a house\" width=\"500\" height=\"366\"> Figure 3 Heat loss via conduction and infiltration\/exfiltration[\/caption]\n\nHeat loss from infiltration (inward flow) and exfiltration (outward flow) is uncontrolled air leakage through joints in the construction and cracks around windows and doors. In the winter, the cold air that infiltrates the building is equal to the amount of hot air that escapes. Conversely, in the summer, the cooler air inside escapes and hot exterior air infiltrates. Infiltration is caused by wind and stack-driven pressure differentials, which prompt air movement within the building envelope. In British Columbia the BC Building Code sets out requirements that are meant to both offset infiltration losses while also delivering fresh air for the health of occupants. The infiltration rate varies greatly depending on climate and the tightness of construction. In general, ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) recommends for small buildings with low infiltration rates (&lt;0.5 air changes per hour, known as \u201ctight\u201d or \u201cairtight\u201d construction) to use mechanical ventilation to ensure good indoor air quality (IAQ). We\u2019ll confine our focus to the determination of the heat lost through infiltration rather than the requirements for mechanical air exchange.\n<h2>Calculating Infiltration Loss<\/h2>\nJust as in the calculation of transmission loss, there is a formula used for calculating losses of heat through infiltration, and it is based upon the fact that air has a specific heat, by volume, of 0.018 as mentioned earlier in the heading \u201cwater vs air as a heating medium\u201d. So, the formula is written as:\n<p style=\"text-align: center;\">Infiltration loss = ACH (# of air changes per hour) \u00d7 0.018 (specific heat of air) \u00d7 DTD ( design temperature difference) \u00d7 room volume (ft\u00b3).<\/p>\nThe determination of an air change rate for a room is somewhat arbitrary, in that there are many factors at play. For our purposes within this learning guide, we will use the Air Change Table found in TECA\u2019s literature below as our benchmark.\n<table class=\"grid\" style=\"border-collapse: collapse; width: 100%;\" border=\"0\"><caption>Air Change Table (courtesy of TECA BC)<\/caption>\n<tbody>\n<tr>\n<th style=\"width: 60%;\" scope=\"col\">Description<\/th>\n<th style=\"width: 20%;\" scope=\"col\">Infiltration Rate<\/th>\n<th style=\"width: 20%;\" scope=\"col\">AC Factor*<\/th>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">R2000 Dwellings ONLY w\/fully distributed ventilation systems (HRV's)<\/td>\n<td style=\"width: 20%;\">[latex]\\dfrac{1}{3}[\/latex] ACH (air change\/hr)<\/td>\n<td style=\"width: 20%;\">.005<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Rooms w\/windows on 1 side only<\/td>\n<td style=\"width: 20%;\">[latex]\\dfrac{1}{2}[\/latex] ACH<\/td>\n<td style=\"width: 20%;\">.009<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Rooms w\/windows on 2 sides<\/td>\n<td style=\"width: 20%;\">[latex]\\dfrac{2}{3}[\/latex] ACH<\/td>\n<td style=\"width: 20%;\">.012<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Rooms w\/windows on 3 sides<\/td>\n<td style=\"width: 20%;\">1 ACH<\/td>\n<td style=\"width: 20%;\">.018<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Entrance Halls<\/td>\n<td style=\"width: 20%;\">1 ACH<\/td>\n<td style=\"width: 20%;\">.018<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Sum rooms w\/windows or doors on three sides<\/td>\n<td style=\"width: 20%;\">[latex]1\\dfrac{1}{2}[\/latex] ACH<\/td>\n<td style=\"width: 20%;\">.027<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Rooms w\/fireplace (except sealed combustion units_<\/td>\n<td style=\"width: 20%;\">1 \u2013 [latex]1\\dfrac{1}{2}[\/latex] ACH<\/td>\n<td style=\"width: 20%;\">.018 \u2013 .027<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n*[latex]\\text{Air Change Factor}=\\dfrac{\\text{Infiltration Rate}}{60}\\times 1.08[\/latex]\n\n[latex]\\text{For Example:} \\dfrac{\\frac{1}{2} \\text{ACH}}{60} \\times 1.08 = .009[\/latex]\n\nAs shown in the air change table above, air change rates vary from [latex]\\dfrac{1}{3}[\/latex] air changes per hour (ACH) to 1 \u00bd ACH. The choice of which one to use for a room comes down to determining how many exterior walls in that room have openings (doors or windows) and the type of room it is. For example, if a corner bedroom has two exterior walls but only one of them has windows, it would be classified as having \u00bd ACH. If the bedroom were 8 ft \u00d7 10 ft \u00d7 8 ft high, its volume would be 640 ft\u00b3. If \u00bd of the room\u2019s air volume needed to be reheated every hour, we would need to heat 320 ft\u00b3 of that room\u2019s air. Rather than split a room\u2019s volume into [latex]\\dfrac{1}{3}[\/latex], \u00bd, etc., we instead leave the room volume alone and adjust the specific heat value for air which is shown in the far-right column. What would otherwise have been a calculation of (640 ft\u00b3 \u00d7 [latex]\\dfrac{1}{2}[\/latex]) \u00d7 0.018 \u00d7 DTD = BTUH infiltration loss, would then become 640 ft\u00b3 \u00d7 (0.018 \u00d7 0.5) \u00d7 DTD = BTUH infiltration loss. The net result is the same, however the specific heat value is altered to be a multiplier instead of using only a portion of the room\u2019s volume. This also makes it easier for use in the formulas that are in use within the TECA heat loss software programs.\n\nAn entrance hall, which is a room with an outside door that is being used frequently, would have a higher rate of air exchange than, say, a bedroom. It is listed at 1 ACH. Solariums (sun rooms), with a lot of glass area, and rooms with wood-burning fireplaces, have an even greater expectation of exfiltration loss, so are listed as 1 \u00bd ACH.\n\nAs you can see from Table 3 above, the determination of which factor to use when performing an infiltration loss using the TECA guidelines is simply reduced to identifying how many exposed walls in that room have openings (doors or windows) and what type of space it is.\n<h1>Additional Heat Losses<\/h1>\n<span lang=\"en-US\" xml:lang=\"en-US\">Hot water heating systems may be designed to provide heat for other services or equipment such as:<\/span>\n<ul>\n \t<li><span lang=\"en-US\" xml:lang=\"en-US\">domestic hot<\/span> <span lang=\"en-US\" xml:lang=\"en-US\">water<\/span><\/li>\n \t<li><span lang=\"en-US\" xml:lang=\"en-US\">swimming<\/span> <span lang=\"en-US\" xml:lang=\"en-US\">pool<\/span><\/li>\n \t<li><span lang=\"en-US\" xml:lang=\"en-US\">hot tub<\/span><\/li>\n \t<li><span lang=\"en-US\" xml:lang=\"en-US\">outdoor radiant panels for melting<\/span> <span lang=\"en-US\" xml:lang=\"en-US\">snow<\/span><\/li>\n<\/ul>\nThe heat loss for these services and equipment must be determined in an appropriate manner, and in some but not all cases added to the total. A swimming pool is a good example of not having its heat load added to that of the building because, in most cases, swimming pools are shut down and not used in the heating season. The energy needed for heating of the domestic hot water can be prioritized over the heat needed for the building, using the rationale that for the period of time that the heating plant is directing energy to the domestic water, the building can \u201ccoast\u201d on its retained heat. In this way, the domestic water can be heated instead of the building, so that there is no additional heat needed.\n\nA hot tub\u2019s heat load would certainly be added to that of the building because they are often used and enjoyed more in the heating season, and the need to add a snow melting system\u2019s load onto that of the building is also obvious.\n\nCalculation of the loads for swimming pools, hot tubs and snow melt will not be part of this learning package.\n<h1>Oversizing the Heating System<\/h1>\nThere are many conflicting thoughts on determining the size of the heating plant and components. Some heating professionals will add 15 to 30% to the heat load to compensate for other losses within the system, such as heat loss through the piping (\u201cpiping tax\u201d) and additional capacity required for start-up of a cold system (\u201cwarm-up allowance\u201d or \u201cpickup allowance\u201d). The extra capacity also guarantees sufficient heat if the outdoor temperature drops below the ODT, if use patterns cause additional heat losses, and if the residents prefer a temperature above the IDT.\n\nOther professionals claim that these extra losses are minimal and that the heating system rarely runs at design conditions, so it is already in fact oversized. This rationale results in a lower installation cost. Those professionals would allow for 100% of the calculated heat load for the building and no more when selecting a heat plant. Also keep in mind that, no matter which sizing rationale is used, boiler inputs normally increase in increments of 25,000 to 50,000 Btuh, so slightly oversizing the boiler is almost inevitable.\n\nNow complete the self test below.\n<h1>Self-Test 1<\/h1>\n<div class=\"textbox textbox--exercises\"><header class=\"textbox__header\">\n<p class=\"textbox__title\">Self-Test 1<\/p>\n\n<\/header>\n<div class=\"textbox__content\">\n<ol>\n \t<li>Which one of the following is <em>not<\/em> a method of heat loss found in building heating systems?\n<ol type=\"a\">\n \t<li>Conduction<\/li>\n \t<li>Respiration<\/li>\n \t<li>Radiation<\/li>\n \t<li>Convection<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the approximate percentage of heat that a human body loses by radiation?\n<ol type=\"a\">\n \t<li>48<\/li>\n \t<li>30<\/li>\n \t<li>22<\/li>\n \t<li>12<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the phenomenon known as, whereby a person can feel cold because they are sitting too close to a window or exterior door, when the temperature setting in the room is normal?\n<ol type=\"a\">\n \t<li>\u201cWarm 98.6\u201d<\/li>\n \t<li>\u201cCold 98.6\u201d<\/li>\n \t<li>\u201cWarm 70\u201d<\/li>\n \t<li>\u201cCold 70\u201d<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the name given to the set of interior room temperature conditions where the human body feels the most comfort?\n<ol type=\"a\">\n \t<li>The desired setpoint<\/li>\n \t<li>The ideal heat curve<\/li>\n \t<li>The desired heat curve<\/li>\n \t<li>The ideal setpoint<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the temperature that is read on a thermometer indicating?\n<ol type=\"a\">\n \t<li>The quantity of heat present<\/li>\n \t<li>The latent heat present<\/li>\n \t<li>The intensity of heat present<\/li>\n \t<li>The BTUs that are present<\/li>\n<\/ol>\n<\/li>\n \t<li>Which one of the following formulas would be used to calculate the number of BTUS involved in the heating of water within a heating plant, such as a boiler?\n<ol type=\"a\">\n \t<li>BTUS = Mass \u00d7 \u0394T \u00d7 S.H.<\/li>\n \t<li>BTUS = Mass \u00d7 latent heat \u00d7 \u0394T<\/li>\n \t<li>BTUS = Latent heat \u00d7 \u0394T \u00d7 area<\/li>\n \t<li>BTUS = Area \u00d7 \u0394T \u00d7 S.H.<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the \u0394T used in the design of most hot water heating systems that are fed from a boiler?\n<ol type=\"a\">\n \t<li>140\u00b0F<\/li>\n \t<li>90\u00b0F<\/li>\n \t<li>20\u00b0F<\/li>\n \t<li>5\u00b0F<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the minimum return water temperature that should be maintained when using a non-condensing boiler?\n<ol type=\"a\">\n \t<li>20\u00b0F<\/li>\n \t<li>90\u00b0F<\/li>\n \t<li>120\u00b0F<\/li>\n \t<li>140\u00b0F<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the term known as whereby heat is able to be applied to only the areas of a building where it is needed, rather than to the whole building?\n<ol type=\"a\">\n \t<li>Zoning<\/li>\n \t<li>Priority<\/li>\n \t<li>Area selection<\/li>\n \t<li>Heat propagation<\/li>\n<\/ol>\n<\/li>\n \t<li>What would be the \u201cK\u201d value for a material that has an insulating value of \u201cR\u201d = 22?\n<ol type=\"a\">\n \t<li>23<\/li>\n \t<li>22<\/li>\n \t<li>11<\/li>\n \t<li>0.045<\/li>\n<\/ol>\n<\/li>\n \t<li>How many BTUs would be involved in the transfer of heat through 150 ft\u00b2 of a material that has an \u201cR\u201d value of 14 if the temperatures on either side of the material are 72\u00b0F and 5\u00b0F?\n<ol type=\"a\">\n \t<li>704<\/li>\n \t<li>809<\/li>\n \t<li>140,700<\/li>\n \t<li>161,700<\/li>\n<\/ol>\n<\/li>\n \t<li>When designing a heating system, what is the \u201cJanuary 2.5%\u201d value for that geographical area known as?\n<ol type=\"a\">\n \t<li>The required temperature<\/li>\n \t<li>The estimated temperature<\/li>\n \t<li>The indoor design temperature<\/li>\n \t<li>The outdoor design temperature<\/li>\n<\/ol>\n<\/li>\n \t<li>According to the TECA Hydronic System Guidelines, what is an allowable IDT that can be used residentially when performing a heat loss estimate if hydronic radiant panels are intended as the primary source of heat?\n<ol type=\"a\">\n \t<li>140\u00b0F<\/li>\n \t<li>80\u00b0F<\/li>\n \t<li>72\u00b0F<\/li>\n \t<li>68\u00b0F<\/li>\n<\/ol>\n<\/li>\n \t<li>According to Part 9 of the BCBC, what is the allowable IDT for an unfinished basement?\n<ol type=\"a\">\n \t<li>15\u00b0C (59\u00b0F)<\/li>\n \t<li>18\u00b0C (64\u00b0F)<\/li>\n \t<li>20\u00b0C (68\u00b0F)<\/li>\n \t<li>22\u00b0C (72\u00b0F)<\/li>\n<\/ol>\n<\/li>\n \t<li>In heat loss language, what is the term for heat that is lost from a building through conduction?\n<ol type=\"a\">\n \t<li>Radiation<\/li>\n \t<li>Infiltration<\/li>\n \t<li>Convection<\/li>\n \t<li>Transmission<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the term for heat that is lost when cold air makes its way into the building through cracks and imperfections in the building\u2019s envelope?\n<ol type=\"a\">\n \t<li>Radiation<\/li>\n \t<li>Infiltration<\/li>\n \t<li>Conduction<\/li>\n \t<li>Transmission<\/li>\n<\/ol>\n<\/li>\n \t<li>Using Table 1, calculate the \u201cU\u201d value for an exterior wall made up of outside air film on 4\u2033 brick on \u00bd\u2033 plywood sheathing on 2 \u00d7 6 wood studs with fiberglass batt insulation on vapour barrier on \u00bd\u2033 gypsum wall board on inside air film (use average value for fiberglass batt insulation).\n<ol type=\"a\">\n \t<li>0.04<\/li>\n \t<li>0.16<\/li>\n \t<li>0.52<\/li>\n \t<li>22.83<\/li>\n<\/ol>\n<\/li>\n \t<li>According to Table 2 (Heat Loss U-Factors Table), which one of the following double-glazed windows would have the best insulation rating?\n<ol type=\"a\">\n \t<li>[latex]\\dfrac{1}{4}[\/latex]\u2033 air space<\/li>\n \t<li>[latex]\\dfrac{1}{2}[\/latex]\u2033 air space<\/li>\n \t<li>[latex]\\dfrac{5}{8}[\/latex]\u2033 air space<\/li>\n \t<li>Low \u201cE\u201d - argon filled<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the term given to the situation where, for instance, a heated slab-on-grade butts up to the exterior foundation wall, allowing heat to transfer between the two materials more easily than through the surrounding structure?\n<ol type=\"a\">\n \t<li>Infiltration<\/li>\n \t<li>Convection<\/li>\n \t<li>Thermal bridging<\/li>\n \t<li>Thermal connectivity<\/li>\n<\/ol>\n<\/li>\n \t<li>What would be the infiltration loss for a corner bedroom that measures 20 ft \u00d7 15 ft \u00d7 8 ft, has openings on both exterior walls, with an ODT of 5\u00b0F and an IDT of 72\u00b0F?\n<ol type=\"a\">\n \t<li>1,447 BTUH<\/li>\n \t<li>1,930 BTUH<\/li>\n \t<li>2,894 BTUH<\/li>\n \t<li>4,342 BTUH<\/li>\n<\/ol>\n<\/li>\n \t<li>What would be the expected outcome of the rate of heat transfer if the \u0394T between two sides of a wall or ceiling were doubled?\n<ol type=\"a\">\n \t<li>The rate would be halved<\/li>\n \t<li>The rate would stay the same<\/li>\n \t<li>The rate would double<\/li>\n<\/ol>\n<\/li>\n \t<li>What would be the expected outcome of the rate of heat transfer if the \u201cR\u201d value of a material were doubled?\n<ol type=\"a\">\n \t<li>The rate would be halved<\/li>\n \t<li>The rate would stay the same<\/li>\n \t<li>The rate would double<\/li>\n<\/ol>\n<\/li>\n \t<li>A contractor plans to build two identical houses, one in Inuvik and the other in Vancouver. Which one of the following statements would be true?\n<ol type=\"a\">\n \t<li>The Vancouver house\u2019s heat loss will be the greater of the two.<\/li>\n \t<li>The Inuvik house\u2019s heat loss will be the lesser of the two.<\/li>\n \t<li>The IDT for the two houses will be different.<\/li>\n \t<li>The ODT for the two houses will be different.<\/li>\n<\/ol>\n<\/li>\n \t<li>How many air changes per hour (ACH) would a room with openings on 3 sides undergo?\n<ol type=\"a\">\n \t<li>[latex]\\dfrac{1}{3}[\/latex]<\/li>\n \t<li>[latex]\\dfrac{1}{2}[\/latex]<\/li>\n \t<li>1<\/li>\n \t<li>[latex]1\\dfrac{1}{2}[\/latex]<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the \u201cU\u201d value to be used for a framed above-grade wall with stucco veneer with building paper, \u00bd\u2033 wood sheathing, studs, \u00bd\u2033 drywall and R14 insulation?\n<ol type=\"a\">\n \t<li>0.05<\/li>\n \t<li>0.06<\/li>\n \t<li>0.07<\/li>\n \t<li>0.50<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the \u201cR\u201d value of 3 inches of extruded polystyrene?\n<ol type=\"a\">\n \t<li>15.0<\/li>\n \t<li>10.0<\/li>\n \t<li>5.0<\/li>\n \t<li>4.0<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the air change factor to be used for an R2000 dwelling with a fully distributed ventilation system (HRV)?\n<ol type=\"a\">\n \t<li>[latex]\\dfrac{1}{3}[\/latex] ACH<\/li>\n \t<li>[latex]\\dfrac{1}{2}[\/latex]\u00a0ACH<\/li>\n \t<li>[latex]\\dfrac{2}{3}[\/latex] ACH<\/li>\n \t<li>1 ACH<\/li>\n<\/ol>\n<\/li>\n \t<li>What is the ODT to be used when designing a building in Youbou, BC?\n<ol type=\"a\">\n \t<li>22\u00b0C<\/li>\n \t<li>15\u00b0C<\/li>\n \t<li>22\u00b0F<\/li>\n \t<li>15\u00b0F<\/li>\n<\/ol>\n<\/li>\n \t<li>Calculate the heat loss (transmission and infiltration) for a bedroom above a carport if:\n<ul>\n \t<li>the room is 12 feet long \u00d7 11 feet wide \u00d7 8 feet high<\/li>\n \t<li>there is a 3\u2032 \u00d7 5\u2032 window with double pane glazing with [latex]\\dfrac{1}{2}[\/latex]\u2033 air space mounted in each of the two exterior walls<\/li>\n \t<li>walls are stucco with R20 insulation<\/li>\n \t<li>the floor beneath the bedroom has R20 insulation<\/li>\n \t<li>the attic space has R40 insulation<\/li>\n \t<li>the home is being built in Kimberly, BC.<\/li>\n<\/ul>\n<\/li>\n \t<li>What would be the downward loss through a concrete floor that is 8 feet below finish grade if the house is in Powell River and the slab measures 17\u2032 \u2013 6\u2033 wide by 33\u2032 \u2013 3\u2033 long? (Assume an IDT of 65\u00b0F).\n<ol type=\"a\">\n \t<li>1,164 BTUH<\/li>\n \t<li>1,327 BTUH<\/li>\n \t<li>1,732 BTUH<\/li>\n \t<li>1,614 BTUH<\/li>\n<\/ol>\n<\/li>\n<\/ol>\nCheck your answers using the\u00a0<a class=\"internal\" href=\"\/plumbing3f\/back-matter\/self-test-answer-keys\/\">Self-Test Answer Keys<\/a>\u00a0in Appendix 1.\n\n<\/div>\n<\/div>\n<h3>Media Attributions<\/h3>\n<ul>\n \t<li>Figure 1 Slab edge loss by ITA is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/\">CC BY-NC-SA licence<\/a>.<\/li>\n \t<li>Figure 2 Slab edge insulation by ITA is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/\">CC BY-NC-SA licence<\/a>.<\/li>\n \t<li>Figure 3 Heat loss via conduction and infiltration\/exfiltration by ITA is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/\">CC BY-NC-SA licence<\/a>.<\/li>\n<\/ul>","rendered":"<p>Rooms have ceilings, floors, and walls with doors and windows. Transmission losses must be calculated for each surface that has unconditioned space on the other side of it. This means that a floor with a heated room below it would be considered to not have any downward heat loss. The same is said for a ceiling with a heated room above it or a wall that abuts a heated room. In short, only surfaces that separate a heated space from the outdoors need to have heat losses calculated for them.<\/p>\n<h1>Transmission Losses through Windows and Doors (Openings)<\/h1>\n<p>The \u201cU\u201d values used for doors are the same as for windows. A \u201cU\u201d value, based on parameters such as single, double or triple glazed with or without special coatings and fillers, is selected from a table, and multiplied by area in ft\u00b2 and by the DTD. As an example, 48 ft\u00b2 of doors and windows with a \u201cU\u201d value of 0.59 in Penticton would calculate to be 48 \u00d7 0.59 \u00d7 67 = 1,897 BTUH.<\/p>\n<h1>Walls and Openings<\/h1>\n<p>Walls that separate heated (conditioned) spaces from the outdoors are called \u201cexposed walls\u201d, and they will have an area that includes windows and doors. The losses through windows and doors (\u201copenings\u201d) must be calculated separately, as they will have different \u201cU\u201d factors than will the walls themselves (see above). The easiest way to perform an exposed wall calculation is to do a takeoff of the area of the openings first. If a room has a total of 108 ft\u00b2 of openings in its exposed walls, that area would be subtracted from the total area (length \u00d7 height) of the exposed wall. So, an exposed wall that measures 28 feet long by 8 feet high would have a gross area of 224 ft\u00b2. When the openings are subtracted from that gross area, the net area of exposed wall becomes 224 \u2013 108 = 116 ft\u00b2. The heat loss formulas can now be applied to the net wall area. Table 2 lists the \u201cU\u201d values for framed walls whose exterior finishes are lumped together into one category. In other words, it doesn\u2019t matter what the exterior wall finish is \u2013 the \u201cU\u201d value depends upon the \u201cR\u201d value of the insulation in the wall cavities. So, for our exterior wall in Penticton, with a net area of 116 ft\u00b2, using R20 insulation in the walls, the calculation would be 116 \u00d7 0.05 \u00d7 67 = 389 BTUH<\/p>\n<h1>Ceiling and Floor Losses<\/h1>\n<p>Ceiling losses will only be counted for rooms on a top floor, and are listed as either \u201croof with attic space\u201d (normal residential construction using trusses) or \u201cbuilt up roof, no attic space\u201d (typically flat or vaulted roofs) with an insulation value attached to them. Floor losses (other than basements) will only be counted if they are located over unheated space such as an open carport (\u201cwood over exposed space\u201d) or a garage (\u201cwood over enclosed space\u201d). The insulation values will determine the \u201cU\u201d value chosen from the table, and their transmission losses are calculated in the same manner as with openings and exposed walls.<\/p>\n<h1>Thermal Bridging<\/h1>\n<p>Our previous example did not make mention at all of a thermal resistance for the 2 \u00d7 6 studs themselves. This is because they are spaced at either 16\u2033 or 24\u2033 centres along the wall and are difficult to allow for. Some heat load designers will include a small allowance for the studs when coming up with the \u201cU\u201d value for an assembly but this is a matter of designer preference.<\/p>\n<p>The studs that form the support system for walls will have a heat loss through them which is higher than that of the insulation between them. This occurrence is known as \u201cthermal bridging\u201d. By definition, thermal bridging, also known as cold bridging or thermal bypass, is an area or component of an object which has a higher thermal conductivity than the surrounding materials, creating a path of least resistance for heat transfer. Overlooked for a great period of time, thermal bridging has recently come to the forefront of heat load calculations as designers strive to be as accurate and comprehensive as possible in their estimates. Thermal bridging not only causes a loss of heat within the space, it can also cause the warm air inside the space to cool down. When heat attempts to escape a room, it follows the path of least resistance. Likewise, the same process occurs during the summer, only in reverse, allowing heat to enter your otherwise cool building, called heat gain. Thermal bridging happens when a more conductive material allows an easy pathway for heat flow, usually where there is a break in (or penetration of) the insulation. Some common locations include:<\/p>\n<ul>\n<li>The junctions between the wall and the floor, roof, or doors and windows.<\/li>\n<li>The junction between the building and the deck or patio<\/li>\n<li>Penetrations in the building envelope to include pipes or cables<\/li>\n<li>Wood, steel, or concrete envelope components such as foundations, studs, and joists<\/li>\n<li>Recessed lighting<\/li>\n<li>Window and door frames<\/li>\n<li>Areas with gaps in insulation<\/li>\n<\/ul>\n<p>In short, any area where there isn\u2019t a continuous, unbroken layer of insulative material can be considered a thermal break. These areas should be addressed in both the design and construction phase, as studies have show that in an otherwise airtight and insulated home,\u00a0<a href=\"https:\/\/www.kore-system.com\/blog\/thermal-bridging-what-it-is-and-why-you-should-avoid-it\" target=\"_blank\" rel=\"noopener\">thermal bridges can account for a heat loss of up to 30%<\/a>. Whether you\u2019re building a new home or retrofitting an existing structure, care should be taken to avoid unnecessary breaks or penetrations in the building envelope so that the possibility of thermal bridging decreases.<\/p>\n<h1>Slab Edge Loss<\/h1>\n<figure id=\"attachment_38\" aria-describedby=\"caption-attachment-38\" style=\"width: 647px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"size-full wp-image-36\" src=\"https:\/\/opentextbc.ca\/bccantiracistbookclubhub\/wp-content\/uploads\/sites\/405\/2022\/08\/image9.jpeg\" alt=\"\" width=\"647\" height=\"393\" srcset=\"https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image9.jpeg 647w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image9-300x182.jpeg 300w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image9-65x39.jpeg 65w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image9-225x137.jpeg 225w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image9-350x213.jpeg 350w\" sizes=\"auto, (max-width: 647px) 100vw, 647px\" \/><figcaption id=\"caption-attachment-38\" class=\"wp-caption-text\">Figure 1 Slab edge loss<\/figcaption><\/figure>\n<p>The thermal bridging that occurs at the point where the indoor concrete slab meets the concrete foundation wall is almost inevitable. Concrete has a low \u201cR\u201d value and there is little that can be done to mitigate the transmission of large amounts of heat between the two masses. Therefore, there will be a category of heat loss called \u201cslab edge loss\u201d that is calculated when using slab-on-grade construction. The formula is written as:<\/p>\n<p style=\"text-align: center;\">Slab edge length (ft) \u00d7 \u201cU\u201d value \u00d7 \u0394T = BTUH.<\/p>\n<p>The slab edge \u201cU\u201d factor, from the table above, is either 0.69 when using 1\u201d insulation, or 0.53 when 2\u201d insulation is used.<\/p>\n<p>As an example, if a room with slab-on-grade construction had 32 lineal feet of exposed slab edge with 2\u201d insulation and the DTD was 67\u00b0F, the calculated slab edge loss would be 32 \u00d7 0.53 \u00d7 67 = 1,136 BTUH. This would be added to the transmission and infiltration losses for that room.<\/p>\n<p>With radiant floor heating, slab edge insulation is a must. A strip of rigid insulating material such as polystyrene is sandwiched between the two concrete masses to try to reduce the thermal bridging effect. As well, rigid polystyrene (XPS) is commonly attached to the outside of the foundation wall, with a protective sheet of galvanized sheet metal covering it, to further reduce the heat loss through the concrete to the soil and outside air.<\/p>\n<figure id=\"attachment_38\" aria-describedby=\"caption-attachment-38\" style=\"width: 635px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-37 size-full\" src=\"https:\/\/opentextbc.ca\/bccantiracistbookclubhub\/wp-content\/uploads\/sites\/405\/2022\/08\/image10-e1651172470700.jpeg\" alt=\"\" width=\"635\" height=\"519\" srcset=\"https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image10-e1651172470700.jpeg 635w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image10-e1651172470700-300x245.jpeg 300w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image10-e1651172470700-65x53.jpeg 65w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image10-e1651172470700-225x184.jpeg 225w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image10-e1651172470700-350x286.jpeg 350w\" sizes=\"auto, (max-width: 635px) 100vw, 635px\" \/><figcaption id=\"caption-attachment-38\" class=\"wp-caption-text\">Figure 2 Slab edge insulation<\/figcaption><\/figure>\n<h1>Basement Concrete Slab Loss<\/h1>\n<p>If a basement concrete floor is more than 2 feet below finish grade, a downward loss should be calculated. The formula is similar to that for walls, except that the IDT can be lower if desired. Using 65\u00b0F (18\u00b0C) as an allowable value for an unfinished basement, the calculation would be:<\/p>\n<p style=\"text-align: center;\">Area (ft\u00b2) \u00d7 DTD (65 \u2212 ODT) \u00d7 0.04 (\u201cslab below grade\u201d from \u201cU\u201d values table above) = BTUH<\/p>\n<p>If the slab is being heated through radiant means, then the slab temperature is used as the IDT.<\/p>\n<h1>Infiltration\/Exfiltration Loss<\/h1>\n<p>Today\u2019s structures are far more airtight than were their counterparts of 50 years ago. Old wood frame double-hung, single pane windows have long ago given way to double or triple glazed gas-filled reflective windows mounted in vinyl frames. Caulking, weatherstripping and energy-conserving measures make today\u2019s structures far less drafty than ever before. That said, there are still imperfections in building envelopes that will allow heated interior air to escape to the outdoors, or cold outside air to be forced into the living space. These heat losses, which can be classified as due to convection, are simply referred to as \u201cinfiltration losses\u201d.<\/p>\n<figure id=\"attachment_38\" aria-describedby=\"caption-attachment-38\" style=\"width: 500px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-38 size-full\" src=\"https:\/\/opentextbc.ca\/bccantiracistbookclubhub\/wp-content\/uploads\/sites\/405\/2022\/08\/image11-e1651172574272.jpeg\" alt=\"Heat loss from a house\" width=\"500\" height=\"366\" srcset=\"https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image11-e1651172574272.jpeg 500w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image11-e1651172574272-300x220.jpeg 300w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image11-e1651172574272-65x48.jpeg 65w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image11-e1651172574272-225x165.jpeg 225w, https:\/\/opentextbc.ca\/plumbing3f\/wp-content\/uploads\/sites\/405\/2022\/08\/image11-e1651172574272-350x256.jpeg 350w\" sizes=\"auto, (max-width: 500px) 100vw, 500px\" \/><figcaption id=\"caption-attachment-38\" class=\"wp-caption-text\">Figure 3 Heat loss via conduction and infiltration\/exfiltration<\/figcaption><\/figure>\n<p>Heat loss from infiltration (inward flow) and exfiltration (outward flow) is uncontrolled air leakage through joints in the construction and cracks around windows and doors. In the winter, the cold air that infiltrates the building is equal to the amount of hot air that escapes. Conversely, in the summer, the cooler air inside escapes and hot exterior air infiltrates. Infiltration is caused by wind and stack-driven pressure differentials, which prompt air movement within the building envelope. In British Columbia the BC Building Code sets out requirements that are meant to both offset infiltration losses while also delivering fresh air for the health of occupants. The infiltration rate varies greatly depending on climate and the tightness of construction. In general, ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers) recommends for small buildings with low infiltration rates (&lt;0.5 air changes per hour, known as \u201ctight\u201d or \u201cairtight\u201d construction) to use mechanical ventilation to ensure good indoor air quality (IAQ). We\u2019ll confine our focus to the determination of the heat lost through infiltration rather than the requirements for mechanical air exchange.<\/p>\n<h2>Calculating Infiltration Loss<\/h2>\n<p>Just as in the calculation of transmission loss, there is a formula used for calculating losses of heat through infiltration, and it is based upon the fact that air has a specific heat, by volume, of 0.018 as mentioned earlier in the heading \u201cwater vs air as a heating medium\u201d. So, the formula is written as:<\/p>\n<p style=\"text-align: center;\">Infiltration loss = ACH (# of air changes per hour) \u00d7 0.018 (specific heat of air) \u00d7 DTD ( design temperature difference) \u00d7 room volume (ft\u00b3).<\/p>\n<p>The determination of an air change rate for a room is somewhat arbitrary, in that there are many factors at play. For our purposes within this learning guide, we will use the Air Change Table found in TECA\u2019s literature below as our benchmark.<\/p>\n<table class=\"grid\" style=\"border-collapse: collapse; width: 100%;\">\n<caption>Air Change Table (courtesy of TECA BC)<\/caption>\n<tbody>\n<tr>\n<th style=\"width: 60%;\" scope=\"col\">Description<\/th>\n<th style=\"width: 20%;\" scope=\"col\">Infiltration Rate<\/th>\n<th style=\"width: 20%;\" scope=\"col\">AC Factor*<\/th>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">R2000 Dwellings ONLY w\/fully distributed ventilation systems (HRV&#8217;s)<\/td>\n<td style=\"width: 20%;\">[latex]\\dfrac{1}{3}[\/latex] ACH (air change\/hr)<\/td>\n<td style=\"width: 20%;\">.005<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Rooms w\/windows on 1 side only<\/td>\n<td style=\"width: 20%;\">[latex]\\dfrac{1}{2}[\/latex] ACH<\/td>\n<td style=\"width: 20%;\">.009<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Rooms w\/windows on 2 sides<\/td>\n<td style=\"width: 20%;\">[latex]\\dfrac{2}{3}[\/latex] ACH<\/td>\n<td style=\"width: 20%;\">.012<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Rooms w\/windows on 3 sides<\/td>\n<td style=\"width: 20%;\">1 ACH<\/td>\n<td style=\"width: 20%;\">.018<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Entrance Halls<\/td>\n<td style=\"width: 20%;\">1 ACH<\/td>\n<td style=\"width: 20%;\">.018<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Sum rooms w\/windows or doors on three sides<\/td>\n<td style=\"width: 20%;\">[latex]1\\dfrac{1}{2}[\/latex] ACH<\/td>\n<td style=\"width: 20%;\">.027<\/td>\n<\/tr>\n<tr>\n<td style=\"width: 60%;\">Rooms w\/fireplace (except sealed combustion units_<\/td>\n<td style=\"width: 20%;\">1 \u2013 [latex]1\\dfrac{1}{2}[\/latex] ACH<\/td>\n<td style=\"width: 20%;\">.018 \u2013 .027<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>*[latex]\\text{Air Change Factor}=\\dfrac{\\text{Infiltration Rate}}{60}\\times 1.08[\/latex]<\/p>\n<p>[latex]\\text{For Example:} \\dfrac{\\frac{1}{2} \\text{ACH}}{60} \\times 1.08 = .009[\/latex]<\/p>\n<p>As shown in the air change table above, air change rates vary from [latex]\\dfrac{1}{3}[\/latex] air changes per hour (ACH) to 1 \u00bd ACH. The choice of which one to use for a room comes down to determining how many exterior walls in that room have openings (doors or windows) and the type of room it is. For example, if a corner bedroom has two exterior walls but only one of them has windows, it would be classified as having \u00bd ACH. If the bedroom were 8 ft \u00d7 10 ft \u00d7 8 ft high, its volume would be 640 ft\u00b3. If \u00bd of the room\u2019s air volume needed to be reheated every hour, we would need to heat 320 ft\u00b3 of that room\u2019s air. Rather than split a room\u2019s volume into [latex]\\dfrac{1}{3}[\/latex], \u00bd, etc., we instead leave the room volume alone and adjust the specific heat value for air which is shown in the far-right column. What would otherwise have been a calculation of (640 ft\u00b3 \u00d7 [latex]\\dfrac{1}{2}[\/latex]) \u00d7 0.018 \u00d7 DTD = BTUH infiltration loss, would then become 640 ft\u00b3 \u00d7 (0.018 \u00d7 0.5) \u00d7 DTD = BTUH infiltration loss. The net result is the same, however the specific heat value is altered to be a multiplier instead of using only a portion of the room\u2019s volume. This also makes it easier for use in the formulas that are in use within the TECA heat loss software programs.<\/p>\n<p>An entrance hall, which is a room with an outside door that is being used frequently, would have a higher rate of air exchange than, say, a bedroom. It is listed at 1 ACH. Solariums (sun rooms), with a lot of glass area, and rooms with wood-burning fireplaces, have an even greater expectation of exfiltration loss, so are listed as 1 \u00bd ACH.<\/p>\n<p>As you can see from Table 3 above, the determination of which factor to use when performing an infiltration loss using the TECA guidelines is simply reduced to identifying how many exposed walls in that room have openings (doors or windows) and what type of space it is.<\/p>\n<h1>Additional Heat Losses<\/h1>\n<p><span lang=\"en-US\" xml:lang=\"en-US\">Hot water heating systems may be designed to provide heat for other services or equipment such as:<\/span><\/p>\n<ul>\n<li><span lang=\"en-US\" xml:lang=\"en-US\">domestic hot<\/span> <span lang=\"en-US\" xml:lang=\"en-US\">water<\/span><\/li>\n<li><span lang=\"en-US\" xml:lang=\"en-US\">swimming<\/span> <span lang=\"en-US\" xml:lang=\"en-US\">pool<\/span><\/li>\n<li><span lang=\"en-US\" xml:lang=\"en-US\">hot tub<\/span><\/li>\n<li><span lang=\"en-US\" xml:lang=\"en-US\">outdoor radiant panels for melting<\/span> <span lang=\"en-US\" xml:lang=\"en-US\">snow<\/span><\/li>\n<\/ul>\n<p>The heat loss for these services and equipment must be determined in an appropriate manner, and in some but not all cases added to the total. A swimming pool is a good example of not having its heat load added to that of the building because, in most cases, swimming pools are shut down and not used in the heating season. The energy needed for heating of the domestic hot water can be prioritized over the heat needed for the building, using the rationale that for the period of time that the heating plant is directing energy to the domestic water, the building can \u201ccoast\u201d on its retained heat. In this way, the domestic water can be heated instead of the building, so that there is no additional heat needed.<\/p>\n<p>A hot tub\u2019s heat load would certainly be added to that of the building because they are often used and enjoyed more in the heating season, and the need to add a snow melting system\u2019s load onto that of the building is also obvious.<\/p>\n<p>Calculation of the loads for swimming pools, hot tubs and snow melt will not be part of this learning package.<\/p>\n<h1>Oversizing the Heating System<\/h1>\n<p>There are many conflicting thoughts on determining the size of the heating plant and components. Some heating professionals will add 15 to 30% to the heat load to compensate for other losses within the system, such as heat loss through the piping (\u201cpiping tax\u201d) and additional capacity required for start-up of a cold system (\u201cwarm-up allowance\u201d or \u201cpickup allowance\u201d). The extra capacity also guarantees sufficient heat if the outdoor temperature drops below the ODT, if use patterns cause additional heat losses, and if the residents prefer a temperature above the IDT.<\/p>\n<p>Other professionals claim that these extra losses are minimal and that the heating system rarely runs at design conditions, so it is already in fact oversized. This rationale results in a lower installation cost. Those professionals would allow for 100% of the calculated heat load for the building and no more when selecting a heat plant. Also keep in mind that, no matter which sizing rationale is used, boiler inputs normally increase in increments of 25,000 to 50,000 Btuh, so slightly oversizing the boiler is almost inevitable.<\/p>\n<p>Now complete the self test below.<\/p>\n<h1>Self-Test 1<\/h1>\n<div class=\"textbox textbox--exercises\">\n<header class=\"textbox__header\">\n<p class=\"textbox__title\">Self-Test 1<\/p>\n<\/header>\n<div class=\"textbox__content\">\n<ol>\n<li>Which one of the following is <em>not<\/em> a method of heat loss found in building heating systems?\n<ol type=\"a\">\n<li>Conduction<\/li>\n<li>Respiration<\/li>\n<li>Radiation<\/li>\n<li>Convection<\/li>\n<\/ol>\n<\/li>\n<li>What is the approximate percentage of heat that a human body loses by radiation?\n<ol type=\"a\">\n<li>48<\/li>\n<li>30<\/li>\n<li>22<\/li>\n<li>12<\/li>\n<\/ol>\n<\/li>\n<li>What is the phenomenon known as, whereby a person can feel cold because they are sitting too close to a window or exterior door, when the temperature setting in the room is normal?\n<ol type=\"a\">\n<li>\u201cWarm 98.6\u201d<\/li>\n<li>\u201cCold 98.6\u201d<\/li>\n<li>\u201cWarm 70\u201d<\/li>\n<li>\u201cCold 70\u201d<\/li>\n<\/ol>\n<\/li>\n<li>What is the name given to the set of interior room temperature conditions where the human body feels the most comfort?\n<ol type=\"a\">\n<li>The desired setpoint<\/li>\n<li>The ideal heat curve<\/li>\n<li>The desired heat curve<\/li>\n<li>The ideal setpoint<\/li>\n<\/ol>\n<\/li>\n<li>What is the temperature that is read on a thermometer indicating?\n<ol type=\"a\">\n<li>The quantity of heat present<\/li>\n<li>The latent heat present<\/li>\n<li>The intensity of heat present<\/li>\n<li>The BTUs that are present<\/li>\n<\/ol>\n<\/li>\n<li>Which one of the following formulas would be used to calculate the number of BTUS involved in the heating of water within a heating plant, such as a boiler?\n<ol type=\"a\">\n<li>BTUS = Mass \u00d7 \u0394T \u00d7 S.H.<\/li>\n<li>BTUS = Mass \u00d7 latent heat \u00d7 \u0394T<\/li>\n<li>BTUS = Latent heat \u00d7 \u0394T \u00d7 area<\/li>\n<li>BTUS = Area \u00d7 \u0394T \u00d7 S.H.<\/li>\n<\/ol>\n<\/li>\n<li>What is the \u0394T used in the design of most hot water heating systems that are fed from a boiler?\n<ol type=\"a\">\n<li>140\u00b0F<\/li>\n<li>90\u00b0F<\/li>\n<li>20\u00b0F<\/li>\n<li>5\u00b0F<\/li>\n<\/ol>\n<\/li>\n<li>What is the minimum return water temperature that should be maintained when using a non-condensing boiler?\n<ol type=\"a\">\n<li>20\u00b0F<\/li>\n<li>90\u00b0F<\/li>\n<li>120\u00b0F<\/li>\n<li>140\u00b0F<\/li>\n<\/ol>\n<\/li>\n<li>What is the term known as whereby heat is able to be applied to only the areas of a building where it is needed, rather than to the whole building?\n<ol type=\"a\">\n<li>Zoning<\/li>\n<li>Priority<\/li>\n<li>Area selection<\/li>\n<li>Heat propagation<\/li>\n<\/ol>\n<\/li>\n<li>What would be the \u201cK\u201d value for a material that has an insulating value of \u201cR\u201d = 22?\n<ol type=\"a\">\n<li>23<\/li>\n<li>22<\/li>\n<li>11<\/li>\n<li>0.045<\/li>\n<\/ol>\n<\/li>\n<li>How many BTUs would be involved in the transfer of heat through 150 ft\u00b2 of a material that has an \u201cR\u201d value of 14 if the temperatures on either side of the material are 72\u00b0F and 5\u00b0F?\n<ol type=\"a\">\n<li>704<\/li>\n<li>809<\/li>\n<li>140,700<\/li>\n<li>161,700<\/li>\n<\/ol>\n<\/li>\n<li>When designing a heating system, what is the \u201cJanuary 2.5%\u201d value for that geographical area known as?\n<ol type=\"a\">\n<li>The required temperature<\/li>\n<li>The estimated temperature<\/li>\n<li>The indoor design temperature<\/li>\n<li>The outdoor design temperature<\/li>\n<\/ol>\n<\/li>\n<li>According to the TECA Hydronic System Guidelines, what is an allowable IDT that can be used residentially when performing a heat loss estimate if hydronic radiant panels are intended as the primary source of heat?\n<ol type=\"a\">\n<li>140\u00b0F<\/li>\n<li>80\u00b0F<\/li>\n<li>72\u00b0F<\/li>\n<li>68\u00b0F<\/li>\n<\/ol>\n<\/li>\n<li>According to Part 9 of the BCBC, what is the allowable IDT for an unfinished basement?\n<ol type=\"a\">\n<li>15\u00b0C (59\u00b0F)<\/li>\n<li>18\u00b0C (64\u00b0F)<\/li>\n<li>20\u00b0C (68\u00b0F)<\/li>\n<li>22\u00b0C (72\u00b0F)<\/li>\n<\/ol>\n<\/li>\n<li>In heat loss language, what is the term for heat that is lost from a building through conduction?\n<ol type=\"a\">\n<li>Radiation<\/li>\n<li>Infiltration<\/li>\n<li>Convection<\/li>\n<li>Transmission<\/li>\n<\/ol>\n<\/li>\n<li>What is the term for heat that is lost when cold air makes its way into the building through cracks and imperfections in the building\u2019s envelope?\n<ol type=\"a\">\n<li>Radiation<\/li>\n<li>Infiltration<\/li>\n<li>Conduction<\/li>\n<li>Transmission<\/li>\n<\/ol>\n<\/li>\n<li>Using Table 1, calculate the \u201cU\u201d value for an exterior wall made up of outside air film on 4\u2033 brick on \u00bd\u2033 plywood sheathing on 2 \u00d7 6 wood studs with fiberglass batt insulation on vapour barrier on \u00bd\u2033 gypsum wall board on inside air film (use average value for fiberglass batt insulation).\n<ol type=\"a\">\n<li>0.04<\/li>\n<li>0.16<\/li>\n<li>0.52<\/li>\n<li>22.83<\/li>\n<\/ol>\n<\/li>\n<li>According to Table 2 (Heat Loss U-Factors Table), which one of the following double-glazed windows would have the best insulation rating?\n<ol type=\"a\">\n<li>[latex]\\dfrac{1}{4}[\/latex]\u2033 air space<\/li>\n<li>[latex]\\dfrac{1}{2}[\/latex]\u2033 air space<\/li>\n<li>[latex]\\dfrac{5}{8}[\/latex]\u2033 air space<\/li>\n<li>Low \u201cE\u201d &#8211; argon filled<\/li>\n<\/ol>\n<\/li>\n<li>What is the term given to the situation where, for instance, a heated slab-on-grade butts up to the exterior foundation wall, allowing heat to transfer between the two materials more easily than through the surrounding structure?\n<ol type=\"a\">\n<li>Infiltration<\/li>\n<li>Convection<\/li>\n<li>Thermal bridging<\/li>\n<li>Thermal connectivity<\/li>\n<\/ol>\n<\/li>\n<li>What would be the infiltration loss for a corner bedroom that measures 20 ft \u00d7 15 ft \u00d7 8 ft, has openings on both exterior walls, with an ODT of 5\u00b0F and an IDT of 72\u00b0F?\n<ol type=\"a\">\n<li>1,447 BTUH<\/li>\n<li>1,930 BTUH<\/li>\n<li>2,894 BTUH<\/li>\n<li>4,342 BTUH<\/li>\n<\/ol>\n<\/li>\n<li>What would be the expected outcome of the rate of heat transfer if the \u0394T between two sides of a wall or ceiling were doubled?\n<ol type=\"a\">\n<li>The rate would be halved<\/li>\n<li>The rate would stay the same<\/li>\n<li>The rate would double<\/li>\n<\/ol>\n<\/li>\n<li>What would be the expected outcome of the rate of heat transfer if the \u201cR\u201d value of a material were doubled?\n<ol type=\"a\">\n<li>The rate would be halved<\/li>\n<li>The rate would stay the same<\/li>\n<li>The rate would double<\/li>\n<\/ol>\n<\/li>\n<li>A contractor plans to build two identical houses, one in Inuvik and the other in Vancouver. Which one of the following statements would be true?\n<ol type=\"a\">\n<li>The Vancouver house\u2019s heat loss will be the greater of the two.<\/li>\n<li>The Inuvik house\u2019s heat loss will be the lesser of the two.<\/li>\n<li>The IDT for the two houses will be different.<\/li>\n<li>The ODT for the two houses will be different.<\/li>\n<\/ol>\n<\/li>\n<li>How many air changes per hour (ACH) would a room with openings on 3 sides undergo?\n<ol type=\"a\">\n<li>[latex]\\dfrac{1}{3}[\/latex]<\/li>\n<li>[latex]\\dfrac{1}{2}[\/latex]<\/li>\n<li>1<\/li>\n<li>[latex]1\\dfrac{1}{2}[\/latex]<\/li>\n<\/ol>\n<\/li>\n<li>What is the \u201cU\u201d value to be used for a framed above-grade wall with stucco veneer with building paper, \u00bd\u2033 wood sheathing, studs, \u00bd\u2033 drywall and R14 insulation?\n<ol type=\"a\">\n<li>0.05<\/li>\n<li>0.06<\/li>\n<li>0.07<\/li>\n<li>0.50<\/li>\n<\/ol>\n<\/li>\n<li>What is the \u201cR\u201d value of 3 inches of extruded polystyrene?\n<ol type=\"a\">\n<li>15.0<\/li>\n<li>10.0<\/li>\n<li>5.0<\/li>\n<li>4.0<\/li>\n<\/ol>\n<\/li>\n<li>What is the air change factor to be used for an R2000 dwelling with a fully distributed ventilation system (HRV)?\n<ol type=\"a\">\n<li>[latex]\\dfrac{1}{3}[\/latex] ACH<\/li>\n<li>[latex]\\dfrac{1}{2}[\/latex]\u00a0ACH<\/li>\n<li>[latex]\\dfrac{2}{3}[\/latex] ACH<\/li>\n<li>1 ACH<\/li>\n<\/ol>\n<\/li>\n<li>What is the ODT to be used when designing a building in Youbou, BC?\n<ol type=\"a\">\n<li>22\u00b0C<\/li>\n<li>15\u00b0C<\/li>\n<li>22\u00b0F<\/li>\n<li>15\u00b0F<\/li>\n<\/ol>\n<\/li>\n<li>Calculate the heat loss (transmission and infiltration) for a bedroom above a carport if:\n<ul>\n<li>the room is 12 feet long \u00d7 11 feet wide \u00d7 8 feet high<\/li>\n<li>there is a 3\u2032 \u00d7 5\u2032 window with double pane glazing with [latex]\\dfrac{1}{2}[\/latex]\u2033 air space mounted in each of the two exterior walls<\/li>\n<li>walls are stucco with R20 insulation<\/li>\n<li>the floor beneath the bedroom has R20 insulation<\/li>\n<li>the attic space has R40 insulation<\/li>\n<li>the home is being built in Kimberly, BC.<\/li>\n<\/ul>\n<\/li>\n<li>What would be the downward loss through a concrete floor that is 8 feet below finish grade if the house is in Powell River and the slab measures 17\u2032 \u2013 6\u2033 wide by 33\u2032 \u2013 3\u2033 long? (Assume an IDT of 65\u00b0F).\n<ol type=\"a\">\n<li>1,164 BTUH<\/li>\n<li>1,327 BTUH<\/li>\n<li>1,732 BTUH<\/li>\n<li>1,614 BTUH<\/li>\n<\/ol>\n<\/li>\n<\/ol>\n<p>Check your answers using the\u00a0<a class=\"internal\" href=\"\/plumbing3f\/back-matter\/self-test-answer-keys\/\">Self-Test Answer Keys<\/a>\u00a0in Appendix 1.<\/p>\n<\/div>\n<\/div>\n<h3>Media Attributions<\/h3>\n<ul>\n<li>Figure 1 Slab edge loss by ITA is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/\">CC BY-NC-SA licence<\/a>.<\/li>\n<li>Figure 2 Slab edge insulation by ITA is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/\">CC BY-NC-SA licence<\/a>.<\/li>\n<li>Figure 3 Heat loss via conduction and infiltration\/exfiltration by ITA is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/\">CC BY-NC-SA licence<\/a>.<\/li>\n<\/ul>\n","protected":false},"author":123,"menu_order":4,"template":"","meta":{"pb_show_title":"on","pb_short_title":"","pb_subtitle":"Calculating Transmission Loss","pb_authors":[],"pb_section_license":""},"chapter-type":[],"contributor":[],"license":[],"class_list":["post-39","chapter","type-chapter","status-publish","hentry"],"part":21,"_links":{"self":[{"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/pressbooks\/v2\/chapters\/39","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/pressbooks\/v2\/chapters"}],"about":[{"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/wp\/v2\/types\/chapter"}],"author":[{"embeddable":true,"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/wp\/v2\/users\/123"}],"version-history":[{"count":1,"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/pressbooks\/v2\/chapters\/39\/revisions"}],"predecessor-version":[{"id":40,"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/pressbooks\/v2\/chapters\/39\/revisions\/40"}],"part":[{"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/pressbooks\/v2\/parts\/21"}],"metadata":[{"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/pressbooks\/v2\/chapters\/39\/metadata\/"}],"wp:attachment":[{"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/wp\/v2\/media?parent=39"}],"wp:term":[{"taxonomy":"chapter-type","embeddable":true,"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/pressbooks\/v2\/chapter-type?post=39"},{"taxonomy":"contributor","embeddable":true,"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/wp\/v2\/contributor?post=39"},{"taxonomy":"license","embeddable":true,"href":"https:\/\/opentextbc.ca\/plumbing3f\/wp-json\/wp\/v2\/license?post=39"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}