{"id":83,"date":"2024-08-20T15:33:39","date_gmt":"2024-08-20T19:33:39","guid":{"rendered":"https:\/\/opentextbc.ca\/plumbing4e\/?post_type=chapter&#038;p=83"},"modified":"2025-05-05T15:46:16","modified_gmt":"2025-05-05T19:46:16","slug":"describe-electric-motors","status":"publish","type":"chapter","link":"https:\/\/opentextbc.ca\/plumbing4e\/chapter\/describe-electric-motors\/","title":{"raw":"Learning Task 3","rendered":"Learning Task 3"},"content":{"raw":"<h1>Electric Motors<\/h1>\r\nThe earliest sources of electrical energy came from DC (direct current) such as batteries, however, in a direct current system there are some inherent limitations and disadvantages that have spurred on the growth of AC (alternating current) systems as a distribution medium. Over 90% of modern day generated electrical energy is AC, however, this was not an overnight decision. In the late 1880s, a variety of inventions across the United States and Europe led to a full-scale battle between alternating current and direct current distribution.\r\n\r\nThomas Edison, leading the charge for DC, had constructed 121 DC power stations in the United States by 1887 but it was found that, even though he proposed a system of small, local power plants that would power individual neighborhoods or city sections, high voltages could not be easily produced and transmitted. DC power was distributed using three wires from the power plant: +110 volts, 0 volts, and -110 volts. Lights and motors could be connected between either the +110V or -110V socket and 0V (neutral). 110V allowed for some voltage drop between the plant and the load (home, office, etc.) but even though the voltage drop across the power lines was accounted for, power plants needed to be located within 1 mile of the end user. This limitation made power distribution in rural areas extremely difficult, if not impossible.\r\n\r\nA turning point in the battle came when George Westinghouse, a famous industrialist from Pittsburgh, purchased Nikola Tesla's patents for AC motors and transmission the following year. With Tesla's patents, Westinghouse worked to perfect the AC distribution system. The power of steam or water turned turbines which created alternating current, and transformers provided an inexpensive method to step up the voltage of AC to several thousand volts for transmission lines and then back down to usable levels in homes and businesses. At higher voltages, the same power could be transmitted at much lower current levels, which meant less power lost due to resistance in the wires. As a result, large power plants could be located many miles away and service a greater number of people and buildings. Westinghouse won a contract in 1893 to build a hydroelectric dam to harness the power of Niagara Falls and transmit AC to Buffalo, NY. The project was completed on November 16, 1896, and when AC power began to service industries in Buffalo, this milestone marked the decline of DC in the United States. While Europe would adopt an AC standard of 220-240 volts at 50 Hz (\u201cHertz\u201d or old \u201ccycles per second\u201d), the standard in North America for the residential and light commercial users would become 120-240 volts at 60 Hz.\r\n<h2>Electromagnetic Induction<\/h2>\r\nAC systems work because of electromagnetic induction. In the 1830\u2019s it was discovered that a conductor moving through a magnetic field, or a field moving near a conductor, created current and voltage within the conductor, as well as its own magnetic filed.\r\n\r\n[caption id=\"attachment_41\" align=\"aligncenter\" width=\"326\"]<img class=\"wp-image-41 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-2-Inducing-a-current-in-a-conductor-moving-within-a-magnetic-field.png\" alt=\"A labelled diagram of inducing a current in a conductor by moving it within a magnet field. There is a large magnet with two sides (north and south). The copper rod is in between the two sides of the magnet, connected on both ends of a sensitive ammeter. The copper rod moves up and down through the magnetic field. \" width=\"326\" height=\"252\" \/> Figure 1. Inducing a current in a conductor moving within a magnetic field[\/caption]\r\n\r\nIn the illustration above, as the conductor is moved upward, current will be induced in a direction that opposes that movement. If the conductor is then moved downward, the electromagnetic forces created will reverse. Those principles were key to the invention of the electric motor.\r\n<h1>DC and Motors<\/h1>\r\nMotors take electrical energy and convert it into mechanical energy. They can operate on either DC or AC. Small DC motors are used in tools, toys, and appliances. Examples of larger DC motors currently in use are for the propulsion of electric vehicles, in elevators and hoists, and in drives for steel rolling mills. A DC motor is made up of:\r\n<ul>\r\n \t<li>a casing containing a stator with permanent magnets (the stationary part of the motor)<\/li>\r\n \t<li>a shaft protruding from one end to which gears, pulleys and fan blades can be attached<\/li>\r\n \t<li>laminated discs containing at least three coils of wire that are attached to the shaft<\/li>\r\n \t<li>a commutator on the shaft\u2019s end with split rings that connect the coils to brushes, and<\/li>\r\n \t<li>external terminals that are attached to the brushes.<\/li>\r\n<\/ul>\r\nWhen an external circuit is closed and DC voltage is applied to the terminals at the end of the motor, current flows through the brushes into the coils, known as \u201cwindings\u201d, and sets up or \u201cinduces\u201d a magnetic field around them. The magnetic field induced in the windings will be attracted and repelled by the permanent north and south magnetic fields within the stator, and the shaft will begin to rotate. The split rings of the commutator in contact with the brushes causes a reversal of the polarities within the windings as the armature passes a certain point and this maintains the rotation of the armature. If not for the split ring commutator, the motor would reach a point where there is no longer an attraction or repulsion of magnetic forces and rotation would stop. The more sets of coils there are in the armature, the smoother the rotation will be, and the less likely that the motor will stall or lock up when it reaches that state of equilibrium just mentioned. The diagram below shows the internal components of a DC motor, with the shaft and casing omitted for clarity.\r\n\r\n[caption id=\"attachment_42\" align=\"aligncenter\" width=\"350\"]<img class=\"wp-image-42 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-3-DC-motor-components.png\" alt=\"A simplified labeled diagram of a DC motor, focusing on its internal components (excluding the shaft and casing). The diagram highlights key elements essential to the motor\u2019s operation. These include the split-ring commutator, which periodically reverses the current direction to maintain continuous rotation, and a brush, which delivers electrical contact to the rotating commutator. The rotor features four labeled coils (windings) that generate a magnetic field when current flows through them. Surrounding the rotor are the North and South stator magnets, which create a stationary magnetic field that interacts with the rotor\u2019s field, producing motion. \" width=\"350\" height=\"264\" \/> Figure 2. DC motor components[\/caption]\r\n\r\nFor a better understanding of motors and electrical principles, check out the excellent information in some of \u201cThe Engineering Mindset\u201d videos. Here are links to a few of them.\r\n<ul>\r\n \t<li>Alternating Current Basics: <em><a href=\"https:\/\/www.youtube.com\/watch?v=1AaUK6pT_cE&amp;list=RDCMUCk0fGHsCEzGig-rSzkfCjMw&amp;index=6\">How does an Electric Motor work? (DC Motor) [4:49]<\/a><\/em><\/li>\r\n \t<li>AC and DC Electricity: <em><a href=\"https:\/\/www.youtube.com\/watch?v=2jqJZxxX6gQ&amp;list=RDCMUCk0fGHsCEzGig-rSzkfCjMw&amp;index=7\">AC and DC Electricity basics [2:56]<\/a><\/em><\/li>\r\n \t<li>How DC Motors Work: <a href=\"https:\/\/www.youtube.com\/watch?v=1AaUK6pT_cE&amp;list=RDCMUCk0fGHsCEzGig-rSzkfCjMw&amp;index=6\"><em>How does an Electric Motor work? (DC Motor) [4:49]<\/em><\/a><\/li>\r\n \t<li>Induction Motors: <a href=\"https:\/\/www.youtube.com\/watch?v=AOC7uTnxmTI\"><em>Induction Motor Basics [8:38]<\/em><\/a><\/li>\r\n \t<li>How 3-phase Electricity Works: <a href=\"https:\/\/youtu.be\/4oRT7PoXSS0?si=A_X1n-_UUQyg15nJ\"><em>How Three Phase Electricity works - The basics explained [7:52]<\/em><\/a> (originally linked: <em><a href=\"https:\/\/www.youtube.com\/watch?v=2jqJZxxX6gQ&amp;list=RDCMUCk0fGHsCEzGig-rSzkfCjMw&amp;index=7\">AC and DC Electricity basics [2:56]<\/a><\/em>)<\/li>\r\n \t<li>Main electrical panel explained: <a href=\"https:\/\/youtu.be\/UBERduCp3Wo\"><em>Main electrical panel explained - Load center - service panel [10:18]<\/em><\/a><\/li>\r\n<\/ul>\r\nBefore we move on to AC motors, let's quickly recap the operation of a DC motor. The permanent magnet is fixed in place and forms the outside static part of the motor (the stator), while coils of wire carrying the electric current fed to the motor form the rotating part of the motor (the rotor). The interaction between the permanent magnetic field of the stator and the attraction\/repulsion tendencies of the temporary magnetic fields produced by the windings within the rotor is what makes the motor start to spin, and the split-ring commutator changes the polarity of the incoming DC every half rotation which keeps it spinning.\r\n\r\n[caption id=\"attachment_43\" align=\"aligncenter\" width=\"262\"]<img class=\"wp-image-43 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-4-Another-simplified-view-of-a-DC-motor.png\" alt=\"A simplified labelled diagram of a DC motor. The permanent magnet has north and south poles, called field poles. The armature is a coil of wire that rotates counterclockwise between the field poles. The ends of the armature connected to the commutator. \" width=\"262\" height=\"202\" \/> Figure 3. Another simplified view of a DC motor[\/caption]\r\n\r\nIn the interests of adherence to the program outline for the piping trades, we will limit any further study to the basics of AC motors.\r\n<h1>AC Motors<\/h1>\r\nIn an AC motor, windings are arranged around the inside of the casing (the stator), which are designed to produce a rotating magnetic field. Centred within the stator is a solid metal shaft onto which is affixed a conductor (a loop of wire or a coil), a cage made of metal bars, and interconnections between and within them, which makes up a freely rotating metal part (the rotor) that can conduct electricity and become a temporary magnet. Unlike in a DC motor, where power is sent to the coils in the rotor, in an AC motor the outer coils that make up the stator receive the electrical power. The coils are energized in pairs, in sequence, producing a strong magnetic field that is in constant movement around the outside of the motor.\r\n\r\n[caption id=\"attachment_45\" align=\"aligncenter\" width=\"600\"]<img class=\"wp-image-45\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Stator-and-rotor-of-an-AC-motor-e1732053560335.png\" alt=\"A stator (left) and rotor (right). \" width=\"600\" height=\"328\" \/> Figure 4. Stator and rotor of an AC motor[\/caption]\r\n\r\n[caption id=\"attachment_44\" align=\"aligncenter\" width=\"600\"]<img class=\"wp-image-44\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Side-and-end-views-of-an-AC-rotor-1024x376.png\" alt=\"A slide view of an AC rotor (left) and end view of an AC rotor (right). \" width=\"600\" height=\"220\" \/> Figure 5. Side and end views of an AC rotor[\/caption]\r\n\r\nRemember that the rotor, suspended on bearings or bushings inside the magnetic field, is an electrical conductor. The stator\u2019s magnetic field, fed with alternating current, is constantly changing so, according to the laws of electromagnetism, the magnetic field induces an electric current inside the rotor. The current induced in the rotor produces its own magnetic field and, according to another law of electromagnetism (Lenz's Law) tries to stop whatever it is that causes it (the rotating magnetic field) by rotating as well. You can think of the rotor as frantically trying to \"catch up\" with the rotating magnetic field in an effort to eliminate the difference in motion between them. Electromagnetic induction is the key to why a motor spins, and that's why it's called an induction motor.\r\n<h1>3-Phase Power<\/h1>\r\nTo understand three-phase motors, it is useful to first understand three-phase power.\r\n\r\nIn electrical power generation, electricity is produced by using a power source such as water or steam in a turbine to spin a generator that is similar in its components to an electric motor, although much more massive in size. The generator\u2019s size and number of windings create alternating current which changes in amplitude and frequency over time. If shown graphically with the amplitude on the vertical y-axis and time on the horizontal x-axis, the relationship between the voltage or current vs. time for one set of windings (a \u201cphase\u201d), through one complete rotation or \u201ccycle\u201d of the armature (rotor) would resemble a sinusoidal or \u201csine\u201d wave as shown below.\r\n\r\n[caption id=\"attachment_46\" align=\"aligncenter\" width=\"487\"]<img class=\"wp-image-46 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-7-Sine-wave-of-single-phase-alternating-current-and-rotor-position-in-time.png\" alt=\"A graph depicting the single phase of a sine wave and the corresponding rotor position. The X axis is the degrees of rotor rotation and the Y axis is the volts. The sine wave is at 0 volts at 0 degrees, maximum positive volts at 90 degrees, 0 volts at 180 degrees, maximum negative volts at 270 degrees, and 0 volts at 360 degrees. The rotor rotation starts with the South pole on the left and North pole on the right at 0 degrees of rotation. At 90 degrees, the south pole is on the top and north pole is on the bottom. At 180 degrees, the south pole is on the right and the north pole is on the left. At 270 degrees, the south pole is on the bottom and north pole is on the top. At 360 degrees, the south pole is on the left and the north pole is on the right. \" width=\"487\" height=\"379\" \/> Figure 6. Sine wave of single phase alternating current and rotor position in time[\/caption]\r\n\r\nThe graph shown above is the result of one set of windings rotating 360 degrees creating alternating current. Add another 2 sets of windings on the same spinning armature and there will be 3 alternating currents or phases produced simultaneously. If the windings are spaced evenly around the armature, their sine waves will be 120 degrees apart as well.\u00a0 There is nothing magical about three-phase power. It is simply three single phases synchronized and offset by 120 degrees. The diagram below shows the effect of the three sets of windings spinning on the same armature (top illustration) and each of the three windings or \u201cphases\u201d shown by themselves below it.\r\n\r\n[caption id=\"attachment_334\" align=\"aligncenter\" width=\"503\"]<img class=\"wp-image-334\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves.png\" alt=\"Four graphs depict a 3-phase sine wave, and the three different phases separated out. On the first graph, all three sine waves are on one graph. The sine waves are offset by 120 degrees so that the phases are evenly spaced and peak at different times. The second graph depicts the first sine wave alone, coloured in red, and with a phase of 0. The third graph depicts the second sine wave alone, coloured in blue, and with a phase of +120 degrees. And the fourth graph depicts the third phase alone, coloured in green, and with a phase of \u2013120 degrees. \" width=\"503\" height=\"687\" \/> Figure 7. Graph showing sine waves of 3-phase alternating current over time, and individual phases within it[\/caption]\r\n\r\nThe three-phase alternating current leaves the generator and enters a transmission substation at the power plant where large transformers convert the generator's voltage (which is already at the thousands of volts level) up to extremely high voltages for long-distance transmission on the power transmission grid. Typical voltages for long distance transmission are in the range of 155<span style=\"margin-left: 0.25em;\">000<\/span> to 765<span style=\"margin-left: 0.25em;\">000<\/span> volts to reduce line losses. The extremely high voltages are stepped down at distribution stations by transformers and are then fed to different areas surrounding the station at a voltage value somewhere around 7200 volts AC. 3-phase AC electricity is confined in its use to commercial and industrial areas where more power is needed to operate large motors and heaters, so transformers will often reduce the voltage in these applications to around 600 volts of 3-phase power. 3-phase transformers for\u00a0 commercial buildings may be of lower output voltages such as 480 and 400 volts.\r\n\r\nThe 3-phase power can be of either a Delta or a Wye configuration. These terms refer to the way the three secondary coils of the transformer secondary have been connected.\r\n\r\n[caption id=\"attachment_48\" align=\"aligncenter\" width=\"763\"]<img class=\"wp-image-48 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-9-3-phase-Delta-wiring.png\" alt=\"A labeled diagram of a 3-phase Delta wiring. There are three phases and the voltage relationships between all of them are 240 Volts. There are three line currents A, B, and C and they form a triangle. \" width=\"763\" height=\"574\" \/> Figure 8. 3-phase Delta wiring[\/caption]\r\n\r\n3-phase Delta systems are normally used for powering loads that don\u2019t require a neutral, such as large motors or heaters. Generation plants typically send power out through this configuration as there is no need for the expense of a fourth neutral wire over what may be very long distances.\r\n\r\nDistribution transformer secondarys are wired either as Delta or Wye configurations, again usually being determined by the intended uses of the power. The advantage of a Wye configuration is that, with the fourth wire (neutral) it allows the transformer to deliver power for both single-phase as well as 3-phase loads. Note that in the 3-phase Wye diagram below, the line-to-neutral (hot-to-neutral) voltages are all at 120 volts, but the line-to-line (hot-to-hot) voltages are 208 volts. This is because of the phases being 120\u00b0 apart, where, if one of the phases is at peak voltage, the other line isn\u2019t. If two hot lines were 180\u00b0 apart, as they are in 120 volt split-phase residential systems, the line voltage is added together to result in 240 volts, which powers appliances such as clothes dryers, ranges, and hot water tanks. Combining two hot 120-volt phases in a 3-phase system results in 208 volts, which is 120 volts \u00d7 1.732 (the square root of 3 which represents the two phases being 120\u00b0 apart). The explanations and calculations that would be used to illustrate that phenomenon are best left to another time and trade.<a id=\"e2fig9\"><\/a>\r\n\r\n[caption id=\"attachment_49\" align=\"aligncenter\" width=\"579\"]<img class=\"wp-image-49 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-10-3-phase-Wye-wiring.png\" alt=\"A labeled diagram of 3-phase wye wiring. Image description is available.\" width=\"579\" height=\"408\" \/> Figure 9. 3-phase Wye wiring <a href=\"#e2fig10_desc\"><em>[Image Description]<\/em><\/a>[\/caption]\r\n<h1>Split-Phase Power<\/h1>\r\nFor safety\u2019s sake, and due to the absence of motors and other loads that would require a higher and more efficient power supply, houses aren\u2019t fed with 3-phase power. The transformers at the street will step one leg or phase of the incoming power down to 240 volts and will tap a neutral into the middle of the secondary coil. This delivers two 120-volt hot wires that are 180\u00b0 out-of-phase from each other and a neutral to the house, as shown in the diagram below.\r\n\r\n[caption id=\"attachment_50\" align=\"aligncenter\" width=\"246\"]<img class=\"wp-image-50 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-11-Split-phase-power-to-residential-buildings.png\" alt=\"A labelled diagram of a split-phase power to residential buildings, the transformers outside of your home. There are three lines: Line 1 (top), Neutral line (middle), and Line 2 (bottom). The volts between Line 1 and the neutral line are 120 Volts, the volts between the neutral line are 120 volts, and the volts between Line 1 and 2 are 240 volts. \" width=\"246\" height=\"141\" \/> Figure 10. Split-phase power to residential buildings[\/caption]\r\n\r\nWhen the two hot legs (Line 1 and Line 2) are wired to an appliance, the voltage difference between them is 240 volts (+120 minus -120 = 240). Electric hot water tanks are wired with just the two hot leads and no neutral because there is no need for a 120V control circuit. Electric dryers and ranges have their 120V control circuits powered by tapping into one of the 120V hot legs and providing a return path to the panel via the neutral wire, so they are 3-wire circuits (two 120-volt hots and a neutral). A common house panel is shown below. The bus connections are staggered, so any two adjacent breakers will be in contact with the L1 and L2 (main) buses. If both breakers feed an appliance, such as through the red and black wires on the right side of the panel, it will be supplied with 240 volts. The switch levers of the two breakers must be tied together so they operate as one.\r\n\r\n[caption id=\"attachment_51\" align=\"aligncenter\" width=\"446\"]<img class=\"wp-image-51 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-12-House-Panel.jpg\" alt=\"A house panel with the components labelled. The components are: The ground wire, line 1 (black wire, +120 volts), line 2 (red wire, -120 volts), the neutral line (grey wire), main breaker, neutral busses, and main busses. \" width=\"446\" height=\"336\" \/> Figure 11. House Panel[\/caption]\r\n<h1>Induction Motors<\/h1>\r\nInduction motors pass an alternating current through coils in the stator which produces a magnetic field, and the oscillating frequency of the AC supply will cause this magnetic field to rotate. The rotating magnetic field (RMF) will then induce opposing magnetic fields in the rotor and cause useful rotation. Both 3-phase and single-phase use this principle, however, the magnetic field produced by 3-phase current will naturally rotate due to the phases being 120\u00b0 apart. The stator in a 3-phase motor will have a minimum of 2 sets of windings for each phase, as seen in the diagram below.\r\n\r\n[caption id=\"attachment_52\" align=\"aligncenter\" width=\"248\"]<img class=\"wp-image-52 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-13-Stator-showing-3-sets-of-opposed-windings-Aa-Bb-and-Cc.png\" alt=\"A labelled diagram of a stator with 3 sets of windings. The stator is circular with the coils of each set of windings opposite each other (\u201cA\u201d is opposite of \u201ca\u201d, \u201cB\u201d is opposite of \u201cb\u201d, \u201cC\u201d is opposite of \u201cc\u201d). It rotates in an anticlockwise direction and each rotation is 120 degrees and each phase (120-degree rotation) has a minimum of 2 windings (one rotation has windings \u201cA\u201d and \u201cC\u201d. Another rotation has windings \u201cC\u201d and \u201cB\u201d). \" width=\"248\" height=\"224\" \/> Figure 12. Stator showing 3 sets of opposed windings (Aa, Bb and Cc)[\/caption]\r\n\r\nThe coils are on opposite sides of the stator from each other so the powerful magnetic fields resulting from current flowing through them will cause induced current in the rotor and the rotor will spin. The rotor\u2019s direction of rotation can be reversed by reversing the positions of any two of the three incoming power legs on their terminal connections.\r\n<h1>Single-Phase Motors<\/h1>\r\nThe single-phase induction motor is a popular motor with the advantages of being cheap, reliable, and able to connect directly to single-phase power, making them especially common in domestic and small commercial appliances. However, unlike three-phase motors, they are not self-starting and require an additional winding driven by a capacitor to accelerate from a standstill. For an induction motor to start running, a rotating magnetic field (RMF) must be produced in the stator, which induces rotation and torque in the rotor. Since the stator does not physically move, the rotation of the magnetic field is produced by the interaction between electromagnetic forces produced in the stator windings. In a three-phase motor, with each winding supplied by a voltage that is 120 degrees out of phase with the other windings, the sum of the forces produced creates a rotating magnetic field (RMF). This means that three-phase power can induce torque in the rotor at a standstill, and three-phase motors can self-start without additional components.\r\n\r\nHowever, a single-phase induction motor is fed by a single-phase power supply that runs through a single stator winding. One stator winding on its own cannot produce an RMF \u2013 it merely produces a pulsing magnetic field that is made of two opposing fields spaced 180 degrees apart. This creates two problems:\r\n<ul>\r\n \t<li>first, the motor is not self-starting because the magnetic field produced by the stator is not rotating; and<\/li>\r\n \t<li>secondly, although a single winding can drive the motor once it gets up to speed, it does not produce a consistent torque in the rotor during a full revolution, which leads to a loss of efficiency and performance.<\/li>\r\n<\/ul>\r\nThe rotor experiences maximum torque at approximately 10% slip (the difference in rotation between the rotor and the stator winding). Therefore, the rotor will spend a large part of each revolution experiencing very low torque.\r\n<h2>Auxiliary Winding<\/h2>\r\nIn addition to the \u201crun\u201d windings within the stator, single-phase induction motors use a second stator winding to overcome these problems, called an \u2018auxiliary winding\u2019 or \u2018start winding.\u2019 This winding is rotated 90 degrees away from the main winding, and, by means of a capacitor that changes the phase of the supply voltage, it is fed by a voltage that is out of phase with the voltage supplied to the main winding. This means that the interaction between the two windings produces a rotating magnetic field, and the motor can self-start.\r\n\r\nThere are two capacitors with different characteristics used by single-phase induction motors for different aspects of their operation.\r\n<h2>Start Capacitors<\/h2>\r\nA start capacitor is one that is used to provide starting torque to the motor. They are electrolytic capacitors with relatively high losses and low efficiency and are not designed for continuous duty, so it is necessary to disconnect them once the motor gets up to speed using a centrifugal switch or relay of some kind.\r\n\r\n[caption id=\"attachment_53\" align=\"aligncenter\" width=\"400\"]<img class=\"wp-image-53\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-14-Start-left-and-run-right-capacitors.png\" alt=\"A start capacitor and a run capacitor. The start capacitor is a TemCo SC0131 Round Motor Start Capacitor. The run capacitor is a Titan pro 370 motor run capacitor. \" width=\"400\" height=\"280\" \/> Figure 13. Start (left) and run (right) capacitors[\/caption]\r\n\r\nThe flyweights in the centrifugal switch shown below move outward from the shaft and, in doing so, move the collar to which they are attached to the right. This breaks the contacts between the line voltage and the start capacitor of the auxiliary winding. This happens at approximately 75% of the motor\u2019s rated speed.\r\n\r\n&nbsp;\r\n\r\n[caption id=\"attachment_54\" align=\"aligncenter\" width=\"312\"]<img class=\"wp-image-54 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-15-Centrifugal-switch.png\" alt=\"A labelled diagram of a centrifugal switch. The components are the rotor, two flyweights, the collar, and the switch contacts (one to the line, one to the auxiliary winding). The flyweights move back and forth from the rotor shaft, which causes the collar to move right to left. This then pushes the switch contacts and breaks them. \" width=\"312\" height=\"228\" \/> Figure 14. Centrifugal switch[\/caption]\r\n<h2>Run Capacitors<\/h2>\r\nA run capacitor is used to smooth the motor's torque during each revolution, increasing efficiency and performance. It is usually much smaller than a start capacitor and of the oil-filled type to reduce energy losses.\r\n<h2>Limitations of Single-Phase Motors<\/h2>\r\nEven with the additional auxiliary winding, a single-phase induction motor suffers from several limitations compared to a three-phase motor. The phase shift provided by a run capacitor changes with the motor's speed, which means efficiency is not consistent as the motor changes speed. Efficiency is also affected by RMF being produced by two stator windings. It is not as close to a perfect circle as a three-phase RMF, meaning that torque still varies considerably during each revolution, reducing performance and increasing vibration. The components required to make single-phase induction motors self-starting, including the capacitors and centrifugal switch, provide an opportunity for thermal and mechanical wear to create maintenance problems.\r\n<h1>Induction Motors and \u201cSlip\u201d<\/h1>\r\nBoth single- and three-phase motors are also known as \u201casynchronous\u201d induction motors, as the frequency of their AC current does not directly match the number of rotations of the output shaft. This phenomenon is known as \u201cslip\u201d and occurs because the rotor is always playing a magnetic game of \u201ccatch-up\u201d with the RMF. The existence of slip means precise timing is difficult with induction motors. Slip is acceptable in situations where precise timing isn\u2019t required.\r\n<h1>Synchronous Motors<\/h1>\r\nSynchronous motors cover the bases that induction motors cannot, namely their \u201casynchronous\u201d nature. Synchronous motors match the output rotational frequency to the input AC frequency, allowing designers to use these motors in precisely timed applications, such as clocks, rolling mills, record players, and more. They accomplish this feat by linking the magnetic poles (the north-south pairs in every magnetic field) of the stator and rotor, so that the stator RMF will turn the rotor at exact, synchronous speeds. Synchronous motors, while generally more expensive than induction motors, sport higher efficiencies. The lack of complexity of induction motors is the best advantage that they have over synchronous designs. They are very simple to manufacture, operate, and maintain, and is why induction motors are by and large less expensive than synchronous motors. Conversely, implementing a synchronous machine requires a more complex rotor, which is more difficult to manufacture\/repair, and requires additional circuits that must be bought and installed so that these motors can operate effectively.\r\n\r\nIn some cases, synchronous motors can achieve efficiencies of &gt;90% and are generally more energy-efficient than induction motors. The efficiency depends on the specific motor type and size, but the lack of slip in synchronous motors means there is less energy lost in converting between electrical energy and mechanical energy. Finally, a common theme between synchronous motors and induction motors is their price separation. For reasons previously explained, synchronous motors are more expensive to produce, implement, maintain, and repair than induction motors, and so are less commonly used.\r\n<h1>Speed Control for Motors<\/h1>\r\nA variable frequency drive (VFD) is a type of motor controller that adjusts the speed of an electric motor by varying the frequency and voltage supplied to it. Other names for a VFD are variable speed drive, adjustable speed drive, adjustable frequency drive, AC drive, microdrive, and inverter.\r\n\r\nFrequency (or hertz) is directly related to the motor\u2019s speed (RPMs). In other words, the faster the frequency, the faster the RPMs. If an application does not require an electric motor to run at full speed, the VFD can be used to ramp down the frequency and voltage to meet the requirements of the electric motor\u2019s load. As the application\u2019s motor speed requirements change, the VFD can simply turn up or down the motor speed to meet the speed requirement. While VFDs are the standard for speed control of 3-phase motors, slowing down single-phase motors is a more difficult task, especially if it is of the type that uses a centrifugal switch to disconnect the start windings. Always make sure to use a speed control that is recommended for a specific type of motor.\r\n<h1>Motor Control<\/h1>\r\nSmall fractional horsepower single-phase motors used in residential applications are normally controlled using a simple on\/off switch. Large single- and three-phase motors in commercial and industrial applications need more protection due to their relative size and cost. Combination motor controllers are normally used for these motors.\r\n\r\n[caption id=\"attachment_55\" align=\"aligncenter\" width=\"246\"]<img class=\"size-full wp-image-55\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-16-Combination-motor-control.png\" alt=\"\" width=\"246\" height=\"246\" \/> Figure 15. Combination motor control[\/caption]\r\n\r\nThe following are the most fundamental functions that a combination motor controller performs:\r\n\r\n<strong>On\/off control:<\/strong> The starter controls the opening and closing of the power electrical circuit. The switching is done by the main contacts (poles) of the relay, known as a contactor. An electromagnetic coil is energized, which open or close the contacts. The electromagnetic coil has a nominal control voltage and can either be an AC or DC voltage.\r\n\r\n<strong>Short-circuit protection:<\/strong> In industrial applications, normal load current can be up to thousands of amperes and in the case of a short-circuit fault, the fault current can go over 100<span style=\"margin-left: 0.25em;\">000<\/span> amperes, and this can cause severe damage to the equipment. The short-circuit protection disconnects the supply and prevents the potential damage in a safe manner. Short circuit protection is provided by fuses or circuit breakers in a combination motor controller.\r\n\r\n<strong>Overload protection:<\/strong> When a motor draws more current than it is designed to, an overload condition is caused. The main objective of an overload relay is to detect the excess currents and open the circuit to prevent the motor from burning out or overheating. Electronic or electromechanical overload relays are used in combination with a contactor to provide the required overload protection.\r\n\r\n<strong>Disconnecting and breaking:<\/strong> To prevent an unintended restart, it is required to disconnect the motor from the main power circuit. As well, In order to safely perform maintenance on a motor or starter, a motor must be able to be isolated from the power. The disconnect switch of the circuit provides this function. Disconnecting and breaking is provided by a disconnect switch or circuit breaker in a combination motor controller.\r\n\r\nFor an excellent online video that explains the wiring and functions of a single-phase motor starter, watch <em><a href=\"https:\/\/www.youtube.com\/watch?v=7U-DqKQkSPU\">Single Phase Direct Online Starter DOL Wiring Diagram Connections Explained - AM2, AM2S, AM2E [15:24]<\/a><\/em>\r\n\r\nWatch <a href=\"https:\/\/www.youtube.com\/watch?v=h89TTwlNnpY\"><em>Star Delta Starter Explained - Working Principle [11:07]<\/em><\/a>\u00a0for an informative video on the starting controls for 3-phase motors.\r\n<h1>Motor Enclosures<\/h1>\r\nMotors have two basic types of enclosures\u2014open and enclosed. Open enclosures allow for the free flow of air through the motor internals for cooling while those that are enclosed greatly restrict or prohibit the entry of outside air. The basic designs used in applications are described below.\r\n<h2>Open Drip Proof<\/h2>\r\nThe open drip proof (ODP) enclosure is intended for installation in clean and dry environments and tends to be the standard in indoor applications. An internal fan circulates ambient air through the enclosure and provides a highly efficient cooling process.\r\n<h2>Totally Enclosed Fan Cooled<\/h2>\r\nThe totally enclosed fan cooled (TEFC) enclosure is designed for outdoor installation and dirty or dusty indoor applications. Special TEFC designs are also used in processing plants in which periodic wash down is required. Unlike the ODP enclosure, it uses an external fan to force ambient air over the motor's exterior surface.\r\n<h2>Totally Enclosed Air Over<\/h2>\r\nThe totally Enclosed Air Over (TEAO) enclosure is designed for damp or wet environments in which the driven machine provides the air flow required for cooling. A common application is cooling tower fans. TEAO motors often have multiple horsepower ratings, and the usable horsepower depends upon the velocity and temperature of the air flowing over the motor.\r\n<h2>Totally Enclosed Non-Ventilated<\/h2>\r\nThe totally enclosed non-ventilated (TENV) enclosure is designed for dusty environments and is usually limited to 5 horsepower and less. It uses raised fins over the motor surface area to transfer heat to the surrounding air without the aid of an external fan.\r\n<h1>Hazardous Locations<\/h1>\r\nHazardous location motors are a totally enclosed design that are intended for use in potentially dangerous areas. The Class I, Explosion Proof (XP) enclosure is a special type that is designed for use in locations in which potentially explosive liquids and gases may be present. Class II enclosures are used in locations that are subject to combustible dusts, such as coal and grains. The area where the rotor shaft exits the enclosure is designed to contain any sparks that could occur inside the motor enclosure.\r\n<h1>Nameplate Information<\/h1>\r\nNEMA MG-1 requires that certain information be included on the nameplate of all single- and three-phase motors. Typical nameplate information may include, but is not limited to expressions of horsepower, volts, amps, Hz, phase, rpm, insulation class, enclosure, frame size, efficiency, service factor, power factor, duty, ambient, code and design. Most terms are straightforward but there are several that require further explanation. An example of a motor nameplate is shown below. Note that, whenever replacing a motor, a photo of its nameplate passed on to a supplier is the easiest and most advisable way to ensure replacement compatibility.\r\n\r\n[caption id=\"attachment_56\" align=\"aligncenter\" width=\"1024\"]<img class=\"wp-image-56 size-large\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-17-AC-motor-nameplate-1024x637.png\" alt=\"An example of an AC motor nameplate. The information on the plate include: The catalog number, model number, shaft end BRG, OPP end BRG, frame designation (FR), Manufacturer\u2019s type (TYPE), Number of phases (PH), maximum ambient temperature (max amb, degrees Celsius), ID number, insulation system designation (Insul. class), Time rating or duty (duty), WT, Horsepower output (HP), speed at rated load (RPM), service factor (SF), Frequency (HZ), Voltage (Volts) Max KVAR, NEMA nominal efficiency (NEMA NOM EFF), rate load current (AMPS), code letter for locked rotor kVA (CODE), Design letter (DES) - only for medium motors, SF AMPS, PF, and Guaranteed efficiency. \u201cThermally protected\u201d (if motor provides all protection in NEMA Standard MG 1, 12.57) and \u201cOver temp. Proto. ____\u201d and device type number (for motors &gt; 1 hp with over-temperature devices or systems). Note: nameplates may also include the manufacturer\u2019s name and usually its principal location. \" width=\"1024\" height=\"637\" \/> Figure 16. AC motor nameplate[\/caption]\r\n<h1>Efficiency<\/h1>\r\nEfficiency (Eff) defines how well a motor converts electrical energy into mechanical energy. The motor's full load efficiency is shown on the nameplate, and it is often less than the actual maximum efficiency. Maximum motor efficiency typically occurs between 70 percent and 95 percent of full load, and most NEMA motors can be operated as low as 60 percent of full load without any significant loss in efficiency.\r\n<h2>Service Factor<\/h2>\r\nService factor (SF) is a multiplier that indicates the actual horsepower that the motor can deliver over and above the nameplate horsepower. For example, if a 10-horsepower motor has an SF of 1.15, it is designed to deliver 11.5 horsepower without overloading. SF is intended to handle small, intermittent overloads, occasional increases in ambient temperature and periods when the actual voltage is lower than the nameplate voltage.\r\n<h2>Power Factor<\/h2>\r\nPower factor (PF) is the ratio of active power in watts to the apparent power in volt-amps at full load. A motor can be designed for high efficiency or high PF but not both. Since efficiency cannot be enhanced in the field, motors are designed for high efficiency and the trade-off is lower PF.\r\n<h2>Duty<\/h2>\r\nDuty defines the length of time that the motor can operate while meeting its other nameplate ratings. Most industrial motors are rated for continuous duty while certain special application motors will show intermittent run times in minutes. Electrical code definitions for duty are covered in the following section.\r\n<h2>Ambient Temperature<\/h2>\r\nAmbient temperature is the maximum allowable temperature of the air surrounding a motor when it is operated continuously at full load. A typical ambient rating is 40 \u00b0C (104\u00b0F).\r\n<h2>Code Letters<\/h2>\r\nCode letters (A \u2013 V) provide the range of current required (locked rotor current or LRC) during across-the-line starting for a particular motor. The value indicated by the code letter is in units of KVA\/horsepower. A typical industrial motor will require five to seven times the full load current during starting.\r\n<h2>Design Letters<\/h2>\r\nDesign letters (A-D) indicate the shape of the torque curve produced by a particular motor. Design B is the standard for industrial duty motors, Design C provides a higher starting torque while Design D is a high slip motor that provides the highest starting torque. Design A is a special purpose motor that offers the highest pullout torque.\r\n\r\n<img class=\"wp-image-56 alignleft\" src=\"https:\/\/pressbooks.bccampus.ca\/plumbing3e\/wp-content\/uploads\/sites\/1587\/2022\/01\/noun-check-702756.png\" alt=\"\" width=\"50\" height=\"50\" \/>Now complete Self-Test 2 and check your answers.\r\n\r\n&nbsp;\r\n<h1>Self-Test 2<\/h1>\r\n<div class=\"textbox textbox--exercises\"><header class=\"textbox__header\">\r\n<p class=\"textbox__title\">Self-Test 2<\/p>\r\n\r\n<\/header>\r\n<div class=\"textbox__content\">[h5p id=\"4\"]<\/div>\r\n<\/div>\r\n<h1>Media Attributions<\/h1>\r\n<ul>\r\n \t<li>Figure 1. \"Inducing a current in a conductor moving within a magnetic field\" \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\r\n \t<li>Figure 2. \"DC motor components\" \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\r\n \t<li>Figure 3. \"Another simplified view of a DC motor\" \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\r\n \t<li>Figure 4. \"Stator and rotor of an AC motor\" \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\r\n \t<li>Figure 5. \"Side and end views of an AC rotor\" \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\r\n \t<li>Figure 6. \"Sine wave of single phase alternating current and rotor position in time\" \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\r\n \t<li>Figure 7. \"Graph showing sine waves of 3-phase alternating current over time, and individual phases within it\" by BCcampus is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/deed.en\">CC BY-NC-SA licence<\/a>.<\/li>\r\n \t<li>Figure 8. \"3-phase Delta wiring\" by Camosun College is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/deed.en\">CC BY-NC-SA licence<\/a>.<\/li>\r\n \t<li>Figure 9. \"<a href=\"https:\/\/link.springer.com\/chapter\/10.1007\/978-981-97-4492-3_6\">3-phase Wye wiring<\/a>\" by Fulai Yao &amp; Yaming Yao is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by\/4.0\/deed.en\" target=\"_blank\" rel=\"noreferrer noopener\">CC BY 4.0 licence<\/a>.<\/li>\r\n \t<li>Figure 10. \"<a href=\"https:\/\/ijarsct.co.in\/Paper2877.pdf\">Split-phase power to residential buildings<\/a>\" from the International Journal of Advanced Research in Science, Communication, and Technology (IJARSCT) is used for educational purposes under the basis of fair dealing.<\/li>\r\n \t<li>Figure 11. \"House Panel\" by Camosun College is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/deed.en\">CC BY-NC-SA licence<\/a>.<\/li>\r\n \t<li>Figure 12. \"Stator showing 3 sets of opposed windings (Aa, Bb and Cc)\" \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\r\n \t<li>Figure 13. \"Start (left) and run (right) capacitors\"\r\n<ul>\r\n \t<li><a href=\"https:\/\/temcoindustrial.com\/59-71-mfd-uf-electric-motor-start-capacitor-220-250v-250-volt\/\">Start (Left)<\/a>: from TEMCo Industrial LLC is used for educational purposes under the basis of fair dealing.<\/li>\r\n \t<li><a href=\"https:\/\/www.packardonline.com\/titan-series-capacitors\">Run (Right)<\/a>: from Packard is used for educational purposes under the basis of fair dealing.<\/li>\r\n<\/ul>\r\n<\/li>\r\n \t<li>Figure 14. \"Centrifugal switch\" \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\r\n \t<li>Figure 15. \"<a href=\"https:\/\/ca.rs-online.com\/product\/square-d\/8538sdasp6\/70281266\/\">Combination motor control<\/a>\" from RS Industrial Solutions &amp; Electronic Components is used for educational purposes under the basis of fair dealing.<\/li>\r\n \t<li>Figure 16. \"AC motor nameplate\" \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\r\n<\/ul>\r\n<h1>Image Description<\/h1>\r\n<strong><a id=\"e2fig10_desc\"><\/a>Figure 9. \"3-phase Wye wiring\" image description:<\/strong> A labeled diagram of 3-phase wye wiring. On the right side of the diagram, the phases are labeled from top to bottom as Phase A, Phase B, Neutral, and Phase C. The diagram indicates the following voltage relationships:\r\n<ul>\r\n \t<li>208V between Phase A and Phase C<\/li>\r\n \t<li>208V between Phase A and Phase B<\/li>\r\n \t<li>208V between Phase B and Phase C<\/li>\r\n \t<li>120V between Phase B and Neutral<\/li>\r\n \t<li>120V between Neutral and Phase C<\/li>\r\n \t<li>120V from Phase A to Neutral<\/li>\r\n<\/ul>\r\nThe wye connection is shown on the left side of the diagram, where all three phases and the neutral meet at the center of the wye configuration. <a href=\"#e2fig9\"><em>[Return Figure 9]<\/em><\/a>","rendered":"<h1>Electric Motors<\/h1>\n<p>The earliest sources of electrical energy came from DC (direct current) such as batteries, however, in a direct current system there are some inherent limitations and disadvantages that have spurred on the growth of AC (alternating current) systems as a distribution medium. Over 90% of modern day generated electrical energy is AC, however, this was not an overnight decision. In the late 1880s, a variety of inventions across the United States and Europe led to a full-scale battle between alternating current and direct current distribution.<\/p>\n<p>Thomas Edison, leading the charge for DC, had constructed 121 DC power stations in the United States by 1887 but it was found that, even though he proposed a system of small, local power plants that would power individual neighborhoods or city sections, high voltages could not be easily produced and transmitted. DC power was distributed using three wires from the power plant: +110 volts, 0 volts, and -110 volts. Lights and motors could be connected between either the +110V or -110V socket and 0V (neutral). 110V allowed for some voltage drop between the plant and the load (home, office, etc.) but even though the voltage drop across the power lines was accounted for, power plants needed to be located within 1 mile of the end user. This limitation made power distribution in rural areas extremely difficult, if not impossible.<\/p>\n<p>A turning point in the battle came when George Westinghouse, a famous industrialist from Pittsburgh, purchased Nikola Tesla&#8217;s patents for AC motors and transmission the following year. With Tesla&#8217;s patents, Westinghouse worked to perfect the AC distribution system. The power of steam or water turned turbines which created alternating current, and transformers provided an inexpensive method to step up the voltage of AC to several thousand volts for transmission lines and then back down to usable levels in homes and businesses. At higher voltages, the same power could be transmitted at much lower current levels, which meant less power lost due to resistance in the wires. As a result, large power plants could be located many miles away and service a greater number of people and buildings. Westinghouse won a contract in 1893 to build a hydroelectric dam to harness the power of Niagara Falls and transmit AC to Buffalo, NY. The project was completed on November 16, 1896, and when AC power began to service industries in Buffalo, this milestone marked the decline of DC in the United States. While Europe would adopt an AC standard of 220-240 volts at 50 Hz (\u201cHertz\u201d or old \u201ccycles per second\u201d), the standard in North America for the residential and light commercial users would become 120-240 volts at 60 Hz.<\/p>\n<h2>Electromagnetic Induction<\/h2>\n<p>AC systems work because of electromagnetic induction. In the 1830\u2019s it was discovered that a conductor moving through a magnetic field, or a field moving near a conductor, created current and voltage within the conductor, as well as its own magnetic filed.<\/p>\n<figure id=\"attachment_41\" aria-describedby=\"caption-attachment-41\" style=\"width: 326px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-41 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-2-Inducing-a-current-in-a-conductor-moving-within-a-magnetic-field.png\" alt=\"A labelled diagram of inducing a current in a conductor by moving it within a magnet field. There is a large magnet with two sides (north and south). The copper rod is in between the two sides of the magnet, connected on both ends of a sensitive ammeter. The copper rod moves up and down through the magnetic field.\" width=\"326\" height=\"252\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-2-Inducing-a-current-in-a-conductor-moving-within-a-magnetic-field.png 326w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-2-Inducing-a-current-in-a-conductor-moving-within-a-magnetic-field-300x232.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-2-Inducing-a-current-in-a-conductor-moving-within-a-magnetic-field-65x50.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-2-Inducing-a-current-in-a-conductor-moving-within-a-magnetic-field-225x174.png 225w\" sizes=\"auto, (max-width: 326px) 100vw, 326px\" \/><figcaption id=\"caption-attachment-41\" class=\"wp-caption-text\">Figure 1. Inducing a current in a conductor moving within a magnetic field<\/figcaption><\/figure>\n<p>In the illustration above, as the conductor is moved upward, current will be induced in a direction that opposes that movement. If the conductor is then moved downward, the electromagnetic forces created will reverse. Those principles were key to the invention of the electric motor.<\/p>\n<h1>DC and Motors<\/h1>\n<p>Motors take electrical energy and convert it into mechanical energy. They can operate on either DC or AC. Small DC motors are used in tools, toys, and appliances. Examples of larger DC motors currently in use are for the propulsion of electric vehicles, in elevators and hoists, and in drives for steel rolling mills. A DC motor is made up of:<\/p>\n<ul>\n<li>a casing containing a stator with permanent magnets (the stationary part of the motor)<\/li>\n<li>a shaft protruding from one end to which gears, pulleys and fan blades can be attached<\/li>\n<li>laminated discs containing at least three coils of wire that are attached to the shaft<\/li>\n<li>a commutator on the shaft\u2019s end with split rings that connect the coils to brushes, and<\/li>\n<li>external terminals that are attached to the brushes.<\/li>\n<\/ul>\n<p>When an external circuit is closed and DC voltage is applied to the terminals at the end of the motor, current flows through the brushes into the coils, known as \u201cwindings\u201d, and sets up or \u201cinduces\u201d a magnetic field around them. The magnetic field induced in the windings will be attracted and repelled by the permanent north and south magnetic fields within the stator, and the shaft will begin to rotate. The split rings of the commutator in contact with the brushes causes a reversal of the polarities within the windings as the armature passes a certain point and this maintains the rotation of the armature. If not for the split ring commutator, the motor would reach a point where there is no longer an attraction or repulsion of magnetic forces and rotation would stop. The more sets of coils there are in the armature, the smoother the rotation will be, and the less likely that the motor will stall or lock up when it reaches that state of equilibrium just mentioned. The diagram below shows the internal components of a DC motor, with the shaft and casing omitted for clarity.<\/p>\n<figure id=\"attachment_42\" aria-describedby=\"caption-attachment-42\" style=\"width: 350px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-42 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-3-DC-motor-components.png\" alt=\"A simplified labeled diagram of a DC motor, focusing on its internal components (excluding the shaft and casing). The diagram highlights key elements essential to the motor\u2019s operation. These include the split-ring commutator, which periodically reverses the current direction to maintain continuous rotation, and a brush, which delivers electrical contact to the rotating commutator. The rotor features four labeled coils (windings) that generate a magnetic field when current flows through them. Surrounding the rotor are the North and South stator magnets, which create a stationary magnetic field that interacts with the rotor\u2019s field, producing motion.\" width=\"350\" height=\"264\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-3-DC-motor-components.png 350w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-3-DC-motor-components-300x226.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-3-DC-motor-components-65x49.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-3-DC-motor-components-225x170.png 225w\" sizes=\"auto, (max-width: 350px) 100vw, 350px\" \/><figcaption id=\"caption-attachment-42\" class=\"wp-caption-text\">Figure 2. DC motor components<\/figcaption><\/figure>\n<p>For a better understanding of motors and electrical principles, check out the excellent information in some of \u201cThe Engineering Mindset\u201d videos. Here are links to a few of them.<\/p>\n<ul>\n<li>Alternating Current Basics: <em><a href=\"https:\/\/www.youtube.com\/watch?v=1AaUK6pT_cE&amp;list=RDCMUCk0fGHsCEzGig-rSzkfCjMw&amp;index=6\">How does an Electric Motor work? (DC Motor) [4:49]<\/a><\/em><\/li>\n<li>AC and DC Electricity: <em><a href=\"https:\/\/www.youtube.com\/watch?v=2jqJZxxX6gQ&amp;list=RDCMUCk0fGHsCEzGig-rSzkfCjMw&amp;index=7\">AC and DC Electricity basics [2:56]<\/a><\/em><\/li>\n<li>How DC Motors Work: <a href=\"https:\/\/www.youtube.com\/watch?v=1AaUK6pT_cE&amp;list=RDCMUCk0fGHsCEzGig-rSzkfCjMw&amp;index=6\"><em>How does an Electric Motor work? (DC Motor) [4:49]<\/em><\/a><\/li>\n<li>Induction Motors: <a href=\"https:\/\/www.youtube.com\/watch?v=AOC7uTnxmTI\"><em>Induction Motor Basics [8:38]<\/em><\/a><\/li>\n<li>How 3-phase Electricity Works: <a href=\"https:\/\/youtu.be\/4oRT7PoXSS0?si=A_X1n-_UUQyg15nJ\"><em>How Three Phase Electricity works &#8211; The basics explained [7:52]<\/em><\/a> (originally linked: <em><a href=\"https:\/\/www.youtube.com\/watch?v=2jqJZxxX6gQ&amp;list=RDCMUCk0fGHsCEzGig-rSzkfCjMw&amp;index=7\">AC and DC Electricity basics [2:56]<\/a><\/em>)<\/li>\n<li>Main electrical panel explained: <a href=\"https:\/\/youtu.be\/UBERduCp3Wo\"><em>Main electrical panel explained &#8211; Load center &#8211; service panel [10:18]<\/em><\/a><\/li>\n<\/ul>\n<p>Before we move on to AC motors, let&#8217;s quickly recap the operation of a DC motor. The permanent magnet is fixed in place and forms the outside static part of the motor (the stator), while coils of wire carrying the electric current fed to the motor form the rotating part of the motor (the rotor). The interaction between the permanent magnetic field of the stator and the attraction\/repulsion tendencies of the temporary magnetic fields produced by the windings within the rotor is what makes the motor start to spin, and the split-ring commutator changes the polarity of the incoming DC every half rotation which keeps it spinning.<\/p>\n<figure id=\"attachment_43\" aria-describedby=\"caption-attachment-43\" style=\"width: 262px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-43 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-4-Another-simplified-view-of-a-DC-motor.png\" alt=\"A simplified labelled diagram of a DC motor. The permanent magnet has north and south poles, called field poles. The armature is a coil of wire that rotates counterclockwise between the field poles. The ends of the armature connected to the commutator.\" width=\"262\" height=\"202\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-4-Another-simplified-view-of-a-DC-motor.png 262w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-4-Another-simplified-view-of-a-DC-motor-65x50.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-4-Another-simplified-view-of-a-DC-motor-225x173.png 225w\" sizes=\"auto, (max-width: 262px) 100vw, 262px\" \/><figcaption id=\"caption-attachment-43\" class=\"wp-caption-text\">Figure 3. Another simplified view of a DC motor<\/figcaption><\/figure>\n<p>In the interests of adherence to the program outline for the piping trades, we will limit any further study to the basics of AC motors.<\/p>\n<h1>AC Motors<\/h1>\n<p>In an AC motor, windings are arranged around the inside of the casing (the stator), which are designed to produce a rotating magnetic field. Centred within the stator is a solid metal shaft onto which is affixed a conductor (a loop of wire or a coil), a cage made of metal bars, and interconnections between and within them, which makes up a freely rotating metal part (the rotor) that can conduct electricity and become a temporary magnet. Unlike in a DC motor, where power is sent to the coils in the rotor, in an AC motor the outer coils that make up the stator receive the electrical power. The coils are energized in pairs, in sequence, producing a strong magnetic field that is in constant movement around the outside of the motor.<\/p>\n<figure id=\"attachment_45\" aria-describedby=\"caption-attachment-45\" style=\"width: 600px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-45\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Stator-and-rotor-of-an-AC-motor-e1732053560335.png\" alt=\"A stator (left) and rotor (right).\" width=\"600\" height=\"328\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Stator-and-rotor-of-an-AC-motor-e1732053560335.png 806w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Stator-and-rotor-of-an-AC-motor-e1732053560335-300x164.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Stator-and-rotor-of-an-AC-motor-e1732053560335-768x420.png 768w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Stator-and-rotor-of-an-AC-motor-e1732053560335-65x36.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Stator-and-rotor-of-an-AC-motor-e1732053560335-225x123.png 225w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Stator-and-rotor-of-an-AC-motor-e1732053560335-350x192.png 350w\" sizes=\"auto, (max-width: 600px) 100vw, 600px\" \/><figcaption id=\"caption-attachment-45\" class=\"wp-caption-text\">Figure 4. Stator and rotor of an AC motor<\/figcaption><\/figure>\n<figure id=\"attachment_44\" aria-describedby=\"caption-attachment-44\" style=\"width: 600px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-44\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Side-and-end-views-of-an-AC-rotor-1024x376.png\" alt=\"A slide view of an AC rotor (left) and end view of an AC rotor (right).\" width=\"600\" height=\"220\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Side-and-end-views-of-an-AC-rotor-1024x376.png 1024w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Side-and-end-views-of-an-AC-rotor-300x110.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Side-and-end-views-of-an-AC-rotor-768x282.png 768w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Side-and-end-views-of-an-AC-rotor-65x24.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Side-and-end-views-of-an-AC-rotor-225x83.png 225w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Side-and-end-views-of-an-AC-rotor-350x128.png 350w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-5-Side-and-end-views-of-an-AC-rotor.png 1264w\" sizes=\"auto, (max-width: 600px) 100vw, 600px\" \/><figcaption id=\"caption-attachment-44\" class=\"wp-caption-text\">Figure 5. Side and end views of an AC rotor<\/figcaption><\/figure>\n<p>Remember that the rotor, suspended on bearings or bushings inside the magnetic field, is an electrical conductor. The stator\u2019s magnetic field, fed with alternating current, is constantly changing so, according to the laws of electromagnetism, the magnetic field induces an electric current inside the rotor. The current induced in the rotor produces its own magnetic field and, according to another law of electromagnetism (Lenz&#8217;s Law) tries to stop whatever it is that causes it (the rotating magnetic field) by rotating as well. You can think of the rotor as frantically trying to &#8220;catch up&#8221; with the rotating magnetic field in an effort to eliminate the difference in motion between them. Electromagnetic induction is the key to why a motor spins, and that&#8217;s why it&#8217;s called an induction motor.<\/p>\n<h1>3-Phase Power<\/h1>\n<p>To understand three-phase motors, it is useful to first understand three-phase power.<\/p>\n<p>In electrical power generation, electricity is produced by using a power source such as water or steam in a turbine to spin a generator that is similar in its components to an electric motor, although much more massive in size. The generator\u2019s size and number of windings create alternating current which changes in amplitude and frequency over time. If shown graphically with the amplitude on the vertical y-axis and time on the horizontal x-axis, the relationship between the voltage or current vs. time for one set of windings (a \u201cphase\u201d), through one complete rotation or \u201ccycle\u201d of the armature (rotor) would resemble a sinusoidal or \u201csine\u201d wave as shown below.<\/p>\n<figure id=\"attachment_46\" aria-describedby=\"caption-attachment-46\" style=\"width: 487px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-46 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-7-Sine-wave-of-single-phase-alternating-current-and-rotor-position-in-time.png\" alt=\"A graph depicting the single phase of a sine wave and the corresponding rotor position. The X axis is the degrees of rotor rotation and the Y axis is the volts. The sine wave is at 0 volts at 0 degrees, maximum positive volts at 90 degrees, 0 volts at 180 degrees, maximum negative volts at 270 degrees, and 0 volts at 360 degrees. The rotor rotation starts with the South pole on the left and North pole on the right at 0 degrees of rotation. At 90 degrees, the south pole is on the top and north pole is on the bottom. At 180 degrees, the south pole is on the right and the north pole is on the left. At 270 degrees, the south pole is on the bottom and north pole is on the top. At 360 degrees, the south pole is on the left and the north pole is on the right.\" width=\"487\" height=\"379\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-7-Sine-wave-of-single-phase-alternating-current-and-rotor-position-in-time.png 487w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-7-Sine-wave-of-single-phase-alternating-current-and-rotor-position-in-time-300x233.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-7-Sine-wave-of-single-phase-alternating-current-and-rotor-position-in-time-65x51.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-7-Sine-wave-of-single-phase-alternating-current-and-rotor-position-in-time-225x175.png 225w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-7-Sine-wave-of-single-phase-alternating-current-and-rotor-position-in-time-350x272.png 350w\" sizes=\"auto, (max-width: 487px) 100vw, 487px\" \/><figcaption id=\"caption-attachment-46\" class=\"wp-caption-text\">Figure 6. Sine wave of single phase alternating current and rotor position in time<\/figcaption><\/figure>\n<p>The graph shown above is the result of one set of windings rotating 360 degrees creating alternating current. Add another 2 sets of windings on the same spinning armature and there will be 3 alternating currents or phases produced simultaneously. If the windings are spaced evenly around the armature, their sine waves will be 120 degrees apart as well.\u00a0 There is nothing magical about three-phase power. It is simply three single phases synchronized and offset by 120 degrees. The diagram below shows the effect of the three sets of windings spinning on the same armature (top illustration) and each of the three windings or \u201cphases\u201d shown by themselves below it.<\/p>\n<figure id=\"attachment_334\" aria-describedby=\"caption-attachment-334\" style=\"width: 503px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-334\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves.png\" alt=\"Four graphs depict a 3-phase sine wave, and the three different phases separated out. On the first graph, all three sine waves are on one graph. The sine waves are offset by 120 degrees so that the phases are evenly spaced and peak at different times. The second graph depicts the first sine wave alone, coloured in red, and with a phase of 0. The third graph depicts the second sine wave alone, coloured in blue, and with a phase of +120 degrees. And the fourth graph depicts the third phase alone, coloured in green, and with a phase of \u2013120 degrees.\" width=\"503\" height=\"687\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves.png 2711w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves-220x300.png 220w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves-750x1024.png 750w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves-768x1049.png 768w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves-1125x1536.png 1125w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves-1500x2048.png 1500w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves-65x89.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves-225x307.png 225w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Sine-waves-350x478.png 350w\" sizes=\"auto, (max-width: 503px) 100vw, 503px\" \/><figcaption id=\"caption-attachment-334\" class=\"wp-caption-text\">Figure 7. Graph showing sine waves of 3-phase alternating current over time, and individual phases within it<\/figcaption><\/figure>\n<p>The three-phase alternating current leaves the generator and enters a transmission substation at the power plant where large transformers convert the generator&#8217;s voltage (which is already at the thousands of volts level) up to extremely high voltages for long-distance transmission on the power transmission grid. Typical voltages for long distance transmission are in the range of 155<span style=\"margin-left: 0.25em;\">000<\/span> to 765<span style=\"margin-left: 0.25em;\">000<\/span> volts to reduce line losses. The extremely high voltages are stepped down at distribution stations by transformers and are then fed to different areas surrounding the station at a voltage value somewhere around 7200 volts AC. 3-phase AC electricity is confined in its use to commercial and industrial areas where more power is needed to operate large motors and heaters, so transformers will often reduce the voltage in these applications to around 600 volts of 3-phase power. 3-phase transformers for\u00a0 commercial buildings may be of lower output voltages such as 480 and 400 volts.<\/p>\n<p>The 3-phase power can be of either a Delta or a Wye configuration. These terms refer to the way the three secondary coils of the transformer secondary have been connected.<\/p>\n<figure id=\"attachment_48\" aria-describedby=\"caption-attachment-48\" style=\"width: 763px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-48 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-9-3-phase-Delta-wiring.png\" alt=\"A labeled diagram of a 3-phase Delta wiring. There are three phases and the voltage relationships between all of them are 240 Volts. There are three line currents A, B, and C and they form a triangle.\" width=\"763\" height=\"574\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-9-3-phase-Delta-wiring.png 763w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-9-3-phase-Delta-wiring-300x226.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-9-3-phase-Delta-wiring-65x49.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-9-3-phase-Delta-wiring-225x169.png 225w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-9-3-phase-Delta-wiring-350x263.png 350w\" sizes=\"auto, (max-width: 763px) 100vw, 763px\" \/><figcaption id=\"caption-attachment-48\" class=\"wp-caption-text\">Figure 8. 3-phase Delta wiring<\/figcaption><\/figure>\n<p>3-phase Delta systems are normally used for powering loads that don\u2019t require a neutral, such as large motors or heaters. Generation plants typically send power out through this configuration as there is no need for the expense of a fourth neutral wire over what may be very long distances.<\/p>\n<p>Distribution transformer secondarys are wired either as Delta or Wye configurations, again usually being determined by the intended uses of the power. The advantage of a Wye configuration is that, with the fourth wire (neutral) it allows the transformer to deliver power for both single-phase as well as 3-phase loads. Note that in the 3-phase Wye diagram below, the line-to-neutral (hot-to-neutral) voltages are all at 120 volts, but the line-to-line (hot-to-hot) voltages are 208 volts. This is because of the phases being 120\u00b0 apart, where, if one of the phases is at peak voltage, the other line isn\u2019t. If two hot lines were 180\u00b0 apart, as they are in 120 volt split-phase residential systems, the line voltage is added together to result in 240 volts, which powers appliances such as clothes dryers, ranges, and hot water tanks. Combining two hot 120-volt phases in a 3-phase system results in 208 volts, which is 120 volts \u00d7 1.732 (the square root of 3 which represents the two phases being 120\u00b0 apart). The explanations and calculations that would be used to illustrate that phenomenon are best left to another time and trade.<a id=\"e2fig9\"><\/a><\/p>\n<figure id=\"attachment_49\" aria-describedby=\"caption-attachment-49\" style=\"width: 579px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-49 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-10-3-phase-Wye-wiring.png\" alt=\"A labeled diagram of 3-phase wye wiring. Image description is available.\" width=\"579\" height=\"408\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-10-3-phase-Wye-wiring.png 579w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-10-3-phase-Wye-wiring-300x211.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-10-3-phase-Wye-wiring-65x46.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-10-3-phase-Wye-wiring-225x159.png 225w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-10-3-phase-Wye-wiring-350x247.png 350w\" sizes=\"auto, (max-width: 579px) 100vw, 579px\" \/><figcaption id=\"caption-attachment-49\" class=\"wp-caption-text\">Figure 9. 3-phase Wye wiring <a href=\"#e2fig10_desc\"><em>[Image Description]<\/em><\/a><\/figcaption><\/figure>\n<h1>Split-Phase Power<\/h1>\n<p>For safety\u2019s sake, and due to the absence of motors and other loads that would require a higher and more efficient power supply, houses aren\u2019t fed with 3-phase power. The transformers at the street will step one leg or phase of the incoming power down to 240 volts and will tap a neutral into the middle of the secondary coil. This delivers two 120-volt hot wires that are 180\u00b0 out-of-phase from each other and a neutral to the house, as shown in the diagram below.<\/p>\n<figure id=\"attachment_50\" aria-describedby=\"caption-attachment-50\" style=\"width: 246px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-50 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-11-Split-phase-power-to-residential-buildings.png\" alt=\"A labelled diagram of a split-phase power to residential buildings, the transformers outside of your home. There are three lines: Line 1 (top), Neutral line (middle), and Line 2 (bottom). The volts between Line 1 and the neutral line are 120 Volts, the volts between the neutral line are 120 volts, and the volts between Line 1 and 2 are 240 volts.\" width=\"246\" height=\"141\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-11-Split-phase-power-to-residential-buildings.png 246w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-11-Split-phase-power-to-residential-buildings-65x37.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-11-Split-phase-power-to-residential-buildings-225x129.png 225w\" sizes=\"auto, (max-width: 246px) 100vw, 246px\" \/><figcaption id=\"caption-attachment-50\" class=\"wp-caption-text\">Figure 10. Split-phase power to residential buildings<\/figcaption><\/figure>\n<p>When the two hot legs (Line 1 and Line 2) are wired to an appliance, the voltage difference between them is 240 volts (+120 minus -120 = 240). Electric hot water tanks are wired with just the two hot leads and no neutral because there is no need for a 120V control circuit. Electric dryers and ranges have their 120V control circuits powered by tapping into one of the 120V hot legs and providing a return path to the panel via the neutral wire, so they are 3-wire circuits (two 120-volt hots and a neutral). A common house panel is shown below. The bus connections are staggered, so any two adjacent breakers will be in contact with the L1 and L2 (main) buses. If both breakers feed an appliance, such as through the red and black wires on the right side of the panel, it will be supplied with 240 volts. The switch levers of the two breakers must be tied together so they operate as one.<\/p>\n<figure id=\"attachment_51\" aria-describedby=\"caption-attachment-51\" style=\"width: 446px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-51 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-12-House-Panel.jpg\" alt=\"A house panel with the components labelled. The components are: The ground wire, line 1 (black wire, +120 volts), line 2 (red wire, -120 volts), the neutral line (grey wire), main breaker, neutral busses, and main busses.\" width=\"446\" height=\"336\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-12-House-Panel.jpg 446w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-12-House-Panel-300x226.jpg 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-12-House-Panel-65x49.jpg 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-12-House-Panel-225x170.jpg 225w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-12-House-Panel-350x264.jpg 350w\" sizes=\"auto, (max-width: 446px) 100vw, 446px\" \/><figcaption id=\"caption-attachment-51\" class=\"wp-caption-text\">Figure 11. House Panel<\/figcaption><\/figure>\n<h1>Induction Motors<\/h1>\n<p>Induction motors pass an alternating current through coils in the stator which produces a magnetic field, and the oscillating frequency of the AC supply will cause this magnetic field to rotate. The rotating magnetic field (RMF) will then induce opposing magnetic fields in the rotor and cause useful rotation. Both 3-phase and single-phase use this principle, however, the magnetic field produced by 3-phase current will naturally rotate due to the phases being 120\u00b0 apart. The stator in a 3-phase motor will have a minimum of 2 sets of windings for each phase, as seen in the diagram below.<\/p>\n<figure id=\"attachment_52\" aria-describedby=\"caption-attachment-52\" style=\"width: 248px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-52 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-13-Stator-showing-3-sets-of-opposed-windings-Aa-Bb-and-Cc.png\" alt=\"A labelled diagram of a stator with 3 sets of windings. The stator is circular with the coils of each set of windings opposite each other (\u201cA\u201d is opposite of \u201ca\u201d, \u201cB\u201d is opposite of \u201cb\u201d, \u201cC\u201d is opposite of \u201cc\u201d). It rotates in an anticlockwise direction and each rotation is 120 degrees and each phase (120-degree rotation) has a minimum of 2 windings (one rotation has windings \u201cA\u201d and \u201cC\u201d. Another rotation has windings \u201cC\u201d and \u201cB\u201d).\" width=\"248\" height=\"224\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-13-Stator-showing-3-sets-of-opposed-windings-Aa-Bb-and-Cc.png 248w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-13-Stator-showing-3-sets-of-opposed-windings-Aa-Bb-and-Cc-65x59.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-13-Stator-showing-3-sets-of-opposed-windings-Aa-Bb-and-Cc-225x203.png 225w\" sizes=\"auto, (max-width: 248px) 100vw, 248px\" \/><figcaption id=\"caption-attachment-52\" class=\"wp-caption-text\">Figure 12. Stator showing 3 sets of opposed windings (Aa, Bb and Cc)<\/figcaption><\/figure>\n<p>The coils are on opposite sides of the stator from each other so the powerful magnetic fields resulting from current flowing through them will cause induced current in the rotor and the rotor will spin. The rotor\u2019s direction of rotation can be reversed by reversing the positions of any two of the three incoming power legs on their terminal connections.<\/p>\n<h1>Single-Phase Motors<\/h1>\n<p>The single-phase induction motor is a popular motor with the advantages of being cheap, reliable, and able to connect directly to single-phase power, making them especially common in domestic and small commercial appliances. However, unlike three-phase motors, they are not self-starting and require an additional winding driven by a capacitor to accelerate from a standstill. For an induction motor to start running, a rotating magnetic field (RMF) must be produced in the stator, which induces rotation and torque in the rotor. Since the stator does not physically move, the rotation of the magnetic field is produced by the interaction between electromagnetic forces produced in the stator windings. In a three-phase motor, with each winding supplied by a voltage that is 120 degrees out of phase with the other windings, the sum of the forces produced creates a rotating magnetic field (RMF). This means that three-phase power can induce torque in the rotor at a standstill, and three-phase motors can self-start without additional components.<\/p>\n<p>However, a single-phase induction motor is fed by a single-phase power supply that runs through a single stator winding. One stator winding on its own cannot produce an RMF \u2013 it merely produces a pulsing magnetic field that is made of two opposing fields spaced 180 degrees apart. This creates two problems:<\/p>\n<ul>\n<li>first, the motor is not self-starting because the magnetic field produced by the stator is not rotating; and<\/li>\n<li>secondly, although a single winding can drive the motor once it gets up to speed, it does not produce a consistent torque in the rotor during a full revolution, which leads to a loss of efficiency and performance.<\/li>\n<\/ul>\n<p>The rotor experiences maximum torque at approximately 10% slip (the difference in rotation between the rotor and the stator winding). Therefore, the rotor will spend a large part of each revolution experiencing very low torque.<\/p>\n<h2>Auxiliary Winding<\/h2>\n<p>In addition to the \u201crun\u201d windings within the stator, single-phase induction motors use a second stator winding to overcome these problems, called an \u2018auxiliary winding\u2019 or \u2018start winding.\u2019 This winding is rotated 90 degrees away from the main winding, and, by means of a capacitor that changes the phase of the supply voltage, it is fed by a voltage that is out of phase with the voltage supplied to the main winding. This means that the interaction between the two windings produces a rotating magnetic field, and the motor can self-start.<\/p>\n<p>There are two capacitors with different characteristics used by single-phase induction motors for different aspects of their operation.<\/p>\n<h2>Start Capacitors<\/h2>\n<p>A start capacitor is one that is used to provide starting torque to the motor. They are electrolytic capacitors with relatively high losses and low efficiency and are not designed for continuous duty, so it is necessary to disconnect them once the motor gets up to speed using a centrifugal switch or relay of some kind.<\/p>\n<figure id=\"attachment_53\" aria-describedby=\"caption-attachment-53\" style=\"width: 400px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-53\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-14-Start-left-and-run-right-capacitors.png\" alt=\"A start capacitor and a run capacitor. The start capacitor is a TemCo SC0131 Round Motor Start Capacitor. The run capacitor is a Titan pro 370 motor run capacitor.\" width=\"400\" height=\"280\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-14-Start-left-and-run-right-capacitors.png 838w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-14-Start-left-and-run-right-capacitors-300x210.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-14-Start-left-and-run-right-capacitors-768x537.png 768w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-14-Start-left-and-run-right-capacitors-65x45.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-14-Start-left-and-run-right-capacitors-225x157.png 225w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-14-Start-left-and-run-right-capacitors-350x245.png 350w\" sizes=\"auto, (max-width: 400px) 100vw, 400px\" \/><figcaption id=\"caption-attachment-53\" class=\"wp-caption-text\">Figure 13. Start (left) and run (right) capacitors<\/figcaption><\/figure>\n<p>The flyweights in the centrifugal switch shown below move outward from the shaft and, in doing so, move the collar to which they are attached to the right. This breaks the contacts between the line voltage and the start capacitor of the auxiliary winding. This happens at approximately 75% of the motor\u2019s rated speed.<\/p>\n<p>&nbsp;<\/p>\n<figure id=\"attachment_54\" aria-describedby=\"caption-attachment-54\" style=\"width: 312px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-54 size-full\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-15-Centrifugal-switch.png\" alt=\"A labelled diagram of a centrifugal switch. The components are the rotor, two flyweights, the collar, and the switch contacts (one to the line, one to the auxiliary winding). The flyweights move back and forth from the rotor shaft, which causes the collar to move right to left. This then pushes the switch contacts and breaks them.\" width=\"312\" height=\"228\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-15-Centrifugal-switch.png 312w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-15-Centrifugal-switch-300x219.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-15-Centrifugal-switch-65x48.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-15-Centrifugal-switch-225x164.png 225w\" sizes=\"auto, (max-width: 312px) 100vw, 312px\" \/><figcaption id=\"caption-attachment-54\" class=\"wp-caption-text\">Figure 14. Centrifugal switch<\/figcaption><\/figure>\n<h2>Run Capacitors<\/h2>\n<p>A run capacitor is used to smooth the motor&#8217;s torque during each revolution, increasing efficiency and performance. It is usually much smaller than a start capacitor and of the oil-filled type to reduce energy losses.<\/p>\n<h2>Limitations of Single-Phase Motors<\/h2>\n<p>Even with the additional auxiliary winding, a single-phase induction motor suffers from several limitations compared to a three-phase motor. The phase shift provided by a run capacitor changes with the motor&#8217;s speed, which means efficiency is not consistent as the motor changes speed. Efficiency is also affected by RMF being produced by two stator windings. It is not as close to a perfect circle as a three-phase RMF, meaning that torque still varies considerably during each revolution, reducing performance and increasing vibration. The components required to make single-phase induction motors self-starting, including the capacitors and centrifugal switch, provide an opportunity for thermal and mechanical wear to create maintenance problems.<\/p>\n<h1>Induction Motors and \u201cSlip\u201d<\/h1>\n<p>Both single- and three-phase motors are also known as \u201casynchronous\u201d induction motors, as the frequency of their AC current does not directly match the number of rotations of the output shaft. This phenomenon is known as \u201cslip\u201d and occurs because the rotor is always playing a magnetic game of \u201ccatch-up\u201d with the RMF. The existence of slip means precise timing is difficult with induction motors. Slip is acceptable in situations where precise timing isn\u2019t required.<\/p>\n<h1>Synchronous Motors<\/h1>\n<p>Synchronous motors cover the bases that induction motors cannot, namely their \u201casynchronous\u201d nature. Synchronous motors match the output rotational frequency to the input AC frequency, allowing designers to use these motors in precisely timed applications, such as clocks, rolling mills, record players, and more. They accomplish this feat by linking the magnetic poles (the north-south pairs in every magnetic field) of the stator and rotor, so that the stator RMF will turn the rotor at exact, synchronous speeds. Synchronous motors, while generally more expensive than induction motors, sport higher efficiencies. The lack of complexity of induction motors is the best advantage that they have over synchronous designs. They are very simple to manufacture, operate, and maintain, and is why induction motors are by and large less expensive than synchronous motors. Conversely, implementing a synchronous machine requires a more complex rotor, which is more difficult to manufacture\/repair, and requires additional circuits that must be bought and installed so that these motors can operate effectively.<\/p>\n<p>In some cases, synchronous motors can achieve efficiencies of &gt;90% and are generally more energy-efficient than induction motors. The efficiency depends on the specific motor type and size, but the lack of slip in synchronous motors means there is less energy lost in converting between electrical energy and mechanical energy. Finally, a common theme between synchronous motors and induction motors is their price separation. For reasons previously explained, synchronous motors are more expensive to produce, implement, maintain, and repair than induction motors, and so are less commonly used.<\/p>\n<h1>Speed Control for Motors<\/h1>\n<p>A variable frequency drive (VFD) is a type of motor controller that adjusts the speed of an electric motor by varying the frequency and voltage supplied to it. Other names for a VFD are variable speed drive, adjustable speed drive, adjustable frequency drive, AC drive, microdrive, and inverter.<\/p>\n<p>Frequency (or hertz) is directly related to the motor\u2019s speed (RPMs). In other words, the faster the frequency, the faster the RPMs. If an application does not require an electric motor to run at full speed, the VFD can be used to ramp down the frequency and voltage to meet the requirements of the electric motor\u2019s load. As the application\u2019s motor speed requirements change, the VFD can simply turn up or down the motor speed to meet the speed requirement. While VFDs are the standard for speed control of 3-phase motors, slowing down single-phase motors is a more difficult task, especially if it is of the type that uses a centrifugal switch to disconnect the start windings. Always make sure to use a speed control that is recommended for a specific type of motor.<\/p>\n<h1>Motor Control<\/h1>\n<p>Small fractional horsepower single-phase motors used in residential applications are normally controlled using a simple on\/off switch. Large single- and three-phase motors in commercial and industrial applications need more protection due to their relative size and cost. Combination motor controllers are normally used for these motors.<\/p>\n<figure id=\"attachment_55\" aria-describedby=\"caption-attachment-55\" style=\"width: 246px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"size-full wp-image-55\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-16-Combination-motor-control.png\" alt=\"\" width=\"246\" height=\"246\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-16-Combination-motor-control.png 246w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-16-Combination-motor-control-150x150.png 150w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-16-Combination-motor-control-65x65.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-16-Combination-motor-control-225x225.png 225w\" sizes=\"auto, (max-width: 246px) 100vw, 246px\" \/><figcaption id=\"caption-attachment-55\" class=\"wp-caption-text\">Figure 15. Combination motor control<\/figcaption><\/figure>\n<p>The following are the most fundamental functions that a combination motor controller performs:<\/p>\n<p><strong>On\/off control:<\/strong> The starter controls the opening and closing of the power electrical circuit. The switching is done by the main contacts (poles) of the relay, known as a contactor. An electromagnetic coil is energized, which open or close the contacts. The electromagnetic coil has a nominal control voltage and can either be an AC or DC voltage.<\/p>\n<p><strong>Short-circuit protection:<\/strong> In industrial applications, normal load current can be up to thousands of amperes and in the case of a short-circuit fault, the fault current can go over 100<span style=\"margin-left: 0.25em;\">000<\/span> amperes, and this can cause severe damage to the equipment. The short-circuit protection disconnects the supply and prevents the potential damage in a safe manner. Short circuit protection is provided by fuses or circuit breakers in a combination motor controller.<\/p>\n<p><strong>Overload protection:<\/strong> When a motor draws more current than it is designed to, an overload condition is caused. The main objective of an overload relay is to detect the excess currents and open the circuit to prevent the motor from burning out or overheating. Electronic or electromechanical overload relays are used in combination with a contactor to provide the required overload protection.<\/p>\n<p><strong>Disconnecting and breaking:<\/strong> To prevent an unintended restart, it is required to disconnect the motor from the main power circuit. As well, In order to safely perform maintenance on a motor or starter, a motor must be able to be isolated from the power. The disconnect switch of the circuit provides this function. Disconnecting and breaking is provided by a disconnect switch or circuit breaker in a combination motor controller.<\/p>\n<p>For an excellent online video that explains the wiring and functions of a single-phase motor starter, watch <em><a href=\"https:\/\/www.youtube.com\/watch?v=7U-DqKQkSPU\">Single Phase Direct Online Starter DOL Wiring Diagram Connections Explained &#8211; AM2, AM2S, AM2E [15:24]<\/a><\/em><\/p>\n<p>Watch <a href=\"https:\/\/www.youtube.com\/watch?v=h89TTwlNnpY\"><em>Star Delta Starter Explained &#8211; Working Principle [11:07]<\/em><\/a>\u00a0for an informative video on the starting controls for 3-phase motors.<\/p>\n<h1>Motor Enclosures<\/h1>\n<p>Motors have two basic types of enclosures\u2014open and enclosed. Open enclosures allow for the free flow of air through the motor internals for cooling while those that are enclosed greatly restrict or prohibit the entry of outside air. The basic designs used in applications are described below.<\/p>\n<h2>Open Drip Proof<\/h2>\n<p>The open drip proof (ODP) enclosure is intended for installation in clean and dry environments and tends to be the standard in indoor applications. An internal fan circulates ambient air through the enclosure and provides a highly efficient cooling process.<\/p>\n<h2>Totally Enclosed Fan Cooled<\/h2>\n<p>The totally enclosed fan cooled (TEFC) enclosure is designed for outdoor installation and dirty or dusty indoor applications. Special TEFC designs are also used in processing plants in which periodic wash down is required. Unlike the ODP enclosure, it uses an external fan to force ambient air over the motor&#8217;s exterior surface.<\/p>\n<h2>Totally Enclosed Air Over<\/h2>\n<p>The totally Enclosed Air Over (TEAO) enclosure is designed for damp or wet environments in which the driven machine provides the air flow required for cooling. A common application is cooling tower fans. TEAO motors often have multiple horsepower ratings, and the usable horsepower depends upon the velocity and temperature of the air flowing over the motor.<\/p>\n<h2>Totally Enclosed Non-Ventilated<\/h2>\n<p>The totally enclosed non-ventilated (TENV) enclosure is designed for dusty environments and is usually limited to 5 horsepower and less. It uses raised fins over the motor surface area to transfer heat to the surrounding air without the aid of an external fan.<\/p>\n<h1>Hazardous Locations<\/h1>\n<p>Hazardous location motors are a totally enclosed design that are intended for use in potentially dangerous areas. The Class I, Explosion Proof (XP) enclosure is a special type that is designed for use in locations in which potentially explosive liquids and gases may be present. Class II enclosures are used in locations that are subject to combustible dusts, such as coal and grains. The area where the rotor shaft exits the enclosure is designed to contain any sparks that could occur inside the motor enclosure.<\/p>\n<h1>Nameplate Information<\/h1>\n<p>NEMA MG-1 requires that certain information be included on the nameplate of all single- and three-phase motors. Typical nameplate information may include, but is not limited to expressions of horsepower, volts, amps, Hz, phase, rpm, insulation class, enclosure, frame size, efficiency, service factor, power factor, duty, ambient, code and design. Most terms are straightforward but there are several that require further explanation. An example of a motor nameplate is shown below. Note that, whenever replacing a motor, a photo of its nameplate passed on to a supplier is the easiest and most advisable way to ensure replacement compatibility.<\/p>\n<figure id=\"attachment_56\" aria-describedby=\"caption-attachment-56\" style=\"width: 1024px\" class=\"wp-caption aligncenter\"><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-56 size-large\" src=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-17-AC-motor-nameplate-1024x637.png\" alt=\"An example of an AC motor nameplate. The information on the plate include: The catalog number, model number, shaft end BRG, OPP end BRG, frame designation (FR), Manufacturer\u2019s type (TYPE), Number of phases (PH), maximum ambient temperature (max amb, degrees Celsius), ID number, insulation system designation (Insul. class), Time rating or duty (duty), WT, Horsepower output (HP), speed at rated load (RPM), service factor (SF), Frequency (HZ), Voltage (Volts) Max KVAR, NEMA nominal efficiency (NEMA NOM EFF), rate load current (AMPS), code letter for locked rotor kVA (CODE), Design letter (DES) - only for medium motors, SF AMPS, PF, and Guaranteed efficiency. \u201cThermally protected\u201d (if motor provides all protection in NEMA Standard MG 1, 12.57) and \u201cOver temp. Proto. ____\u201d and device type number (for motors &gt; 1 hp with over-temperature devices or systems). Note: nameplates may also include the manufacturer\u2019s name and usually its principal location.\" width=\"1024\" height=\"637\" srcset=\"https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-17-AC-motor-nameplate-1024x637.png 1024w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-17-AC-motor-nameplate-300x187.png 300w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-17-AC-motor-nameplate-768x478.png 768w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-17-AC-motor-nameplate-65x40.png 65w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-17-AC-motor-nameplate-225x140.png 225w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-17-AC-motor-nameplate-350x218.png 350w, https:\/\/opentextbc.ca\/plumbing4e\/wp-content\/uploads\/sites\/465\/2024\/08\/Figure-17-AC-motor-nameplate.png 1090w\" sizes=\"auto, (max-width: 1024px) 100vw, 1024px\" \/><figcaption id=\"caption-attachment-56\" class=\"wp-caption-text\">Figure 16. AC motor nameplate<\/figcaption><\/figure>\n<h1>Efficiency<\/h1>\n<p>Efficiency (Eff) defines how well a motor converts electrical energy into mechanical energy. The motor&#8217;s full load efficiency is shown on the nameplate, and it is often less than the actual maximum efficiency. Maximum motor efficiency typically occurs between 70 percent and 95 percent of full load, and most NEMA motors can be operated as low as 60 percent of full load without any significant loss in efficiency.<\/p>\n<h2>Service Factor<\/h2>\n<p>Service factor (SF) is a multiplier that indicates the actual horsepower that the motor can deliver over and above the nameplate horsepower. For example, if a 10-horsepower motor has an SF of 1.15, it is designed to deliver 11.5 horsepower without overloading. SF is intended to handle small, intermittent overloads, occasional increases in ambient temperature and periods when the actual voltage is lower than the nameplate voltage.<\/p>\n<h2>Power Factor<\/h2>\n<p>Power factor (PF) is the ratio of active power in watts to the apparent power in volt-amps at full load. A motor can be designed for high efficiency or high PF but not both. Since efficiency cannot be enhanced in the field, motors are designed for high efficiency and the trade-off is lower PF.<\/p>\n<h2>Duty<\/h2>\n<p>Duty defines the length of time that the motor can operate while meeting its other nameplate ratings. Most industrial motors are rated for continuous duty while certain special application motors will show intermittent run times in minutes. Electrical code definitions for duty are covered in the following section.<\/p>\n<h2>Ambient Temperature<\/h2>\n<p>Ambient temperature is the maximum allowable temperature of the air surrounding a motor when it is operated continuously at full load. A typical ambient rating is 40 \u00b0C (104\u00b0F).<\/p>\n<h2>Code Letters<\/h2>\n<p>Code letters (A \u2013 V) provide the range of current required (locked rotor current or LRC) during across-the-line starting for a particular motor. The value indicated by the code letter is in units of KVA\/horsepower. A typical industrial motor will require five to seven times the full load current during starting.<\/p>\n<h2>Design Letters<\/h2>\n<p>Design letters (A-D) indicate the shape of the torque curve produced by a particular motor. Design B is the standard for industrial duty motors, Design C provides a higher starting torque while Design D is a high slip motor that provides the highest starting torque. Design A is a special purpose motor that offers the highest pullout torque.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" class=\"wp-image-56 alignleft\" src=\"https:\/\/pressbooks.bccampus.ca\/plumbing3e\/wp-content\/uploads\/sites\/1587\/2022\/01\/noun-check-702756.png\" alt=\"\" width=\"50\" height=\"50\" \/>Now complete Self-Test 2 and check your answers.<\/p>\n<p>&nbsp;<\/p>\n<h1>Self-Test 2<\/h1>\n<div class=\"textbox textbox--exercises\">\n<header class=\"textbox__header\">\n<p class=\"textbox__title\">Self-Test 2<\/p>\n<\/header>\n<div class=\"textbox__content\">\n<div id=\"h5p-4\">\n<div class=\"h5p-iframe-wrapper\"><iframe id=\"h5p-iframe-4\" class=\"h5p-iframe\" data-content-id=\"4\" style=\"height:1px\" src=\"about:blank\" frameBorder=\"0\" scrolling=\"no\" title=\"E2 Self-Test 2\"><\/iframe><\/div>\n<\/div>\n<\/div>\n<\/div>\n<h1>Media Attributions<\/h1>\n<ul>\n<li>Figure 1. &#8220;Inducing a current in a conductor moving within a magnetic field&#8221; \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\n<li>Figure 2. &#8220;DC motor components&#8221; \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\n<li>Figure 3. &#8220;Another simplified view of a DC motor&#8221; \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\n<li>Figure 4. &#8220;Stator and rotor of an AC motor&#8221; \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\n<li>Figure 5. &#8220;Side and end views of an AC rotor&#8221; \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\n<li>Figure 6. &#8220;Sine wave of single phase alternating current and rotor position in time&#8221; \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\n<li>Figure 7. &#8220;Graph showing sine waves of 3-phase alternating current over time, and individual phases within it&#8221; by BCcampus is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/deed.en\">CC BY-NC-SA licence<\/a>.<\/li>\n<li>Figure 8. &#8220;3-phase Delta wiring&#8221; by Camosun College is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/deed.en\">CC BY-NC-SA licence<\/a>.<\/li>\n<li>Figure 9. &#8220;<a href=\"https:\/\/link.springer.com\/chapter\/10.1007\/978-981-97-4492-3_6\">3-phase Wye wiring<\/a>&#8221; by Fulai Yao &amp; Yaming Yao is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by\/4.0\/deed.en\" target=\"_blank\" rel=\"noreferrer noopener\">CC BY 4.0 licence<\/a>.<\/li>\n<li>Figure 10. &#8220;<a href=\"https:\/\/ijarsct.co.in\/Paper2877.pdf\">Split-phase power to residential buildings<\/a>&#8221; from the International Journal of Advanced Research in Science, Communication, and Technology (IJARSCT) is used for educational purposes under the basis of fair dealing.<\/li>\n<li>Figure 11. &#8220;House Panel&#8221; by Camosun College is licensed under a <a href=\"https:\/\/creativecommons.org\/licenses\/by-nc-sa\/4.0\/deed.en\">CC BY-NC-SA licence<\/a>.<\/li>\n<li>Figure 12. &#8220;Stator showing 3 sets of opposed windings (Aa, Bb and Cc)&#8221; \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\n<li>Figure 13. &#8220;Start (left) and run (right) capacitors&#8221;\n<ul>\n<li><a href=\"https:\/\/temcoindustrial.com\/59-71-mfd-uf-electric-motor-start-capacitor-220-250v-250-volt\/\">Start (Left)<\/a>: from TEMCo Industrial LLC is used for educational purposes under the basis of fair dealing.<\/li>\n<li><a href=\"https:\/\/www.packardonline.com\/titan-series-capacitors\">Run (Right)<\/a>: from Packard is used for educational purposes under the basis of fair dealing.<\/li>\n<\/ul>\n<\/li>\n<li>Figure 14. &#8220;Centrifugal switch&#8221; \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\n<li>Figure 15. &#8220;<a href=\"https:\/\/ca.rs-online.com\/product\/square-d\/8538sdasp6\/70281266\/\">Combination motor control<\/a>&#8221; from RS Industrial Solutions &amp; Electronic Components is used for educational purposes under the basis of fair dealing.<\/li>\n<li>Figure 16. &#8220;AC motor nameplate&#8221; \u00a9SkilledTradesBC, Province of British Columbia. These resources are not designed for rework, reuse, remixing, and\/or redistribution; they are to be used solely for the purposes of instruction.<\/li>\n<\/ul>\n<h1>Image Description<\/h1>\n<p><strong><a id=\"e2fig10_desc\"><\/a>Figure 9. &#8220;3-phase Wye wiring&#8221; image description:<\/strong> A labeled diagram of 3-phase wye wiring. On the right side of the diagram, the phases are labeled from top to bottom as Phase A, Phase B, Neutral, and Phase C. The diagram indicates the following voltage relationships:<\/p>\n<ul>\n<li>208V between Phase A and Phase C<\/li>\n<li>208V between Phase A and Phase B<\/li>\n<li>208V between Phase B and Phase C<\/li>\n<li>120V between Phase B and Neutral<\/li>\n<li>120V between Neutral and Phase C<\/li>\n<li>120V from Phase A to Neutral<\/li>\n<\/ul>\n<p>The wye connection is shown on the left side of the diagram, where all three phases and the neutral meet at the center of the wye configuration. <a href=\"#e2fig9\"><em>[Return Figure 9]<\/em><\/a><\/p>\n","protected":false},"author":125,"menu_order":3,"template":"","meta":{"pb_show_title":"on","pb_short_title":"","pb_subtitle":"Describe Electric Motors","pb_authors":[],"pb_section_license":""},"chapter-type":[],"contributor":[],"license":[],"class_list":["post-83","chapter","type-chapter","status-publish","hentry"],"part":39,"_links":{"self":[{"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/pressbooks\/v2\/chapters\/83","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/pressbooks\/v2\/chapters"}],"about":[{"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/wp\/v2\/types\/chapter"}],"author":[{"embeddable":true,"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/wp\/v2\/users\/125"}],"version-history":[{"count":24,"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/pressbooks\/v2\/chapters\/83\/revisions"}],"predecessor-version":[{"id":341,"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/pressbooks\/v2\/chapters\/83\/revisions\/341"}],"part":[{"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/pressbooks\/v2\/parts\/39"}],"metadata":[{"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/pressbooks\/v2\/chapters\/83\/metadata\/"}],"wp:attachment":[{"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/wp\/v2\/media?parent=83"}],"wp:term":[{"taxonomy":"chapter-type","embeddable":true,"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/pressbooks\/v2\/chapter-type?post=83"},{"taxonomy":"contributor","embeddable":true,"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/wp\/v2\/contributor?post=83"},{"taxonomy":"license","embeddable":true,"href":"https:\/\/opentextbc.ca\/plumbing4e\/wp-json\/wp\/v2\/license?post=83"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}