Appendix 1: Self-Test Answer Keys
Competency F1
Self Test 1
- b. Respiration
 - a. 48
 - d. “Cold 70”
 - b. The ideal heat curve
 - c. The intensity of heat present
 - a. Mass (weight in pounds) × ΔT (in degrees F) × S.H. (specific heat)
 - c. 20°F
 - d. 140°F
 - a. Zoning
 - d. 0.045 (1 ÷ 22)
 - a. 704150 ft² × (1 ÷ 14) × (72 – 5) = 150 × 0.07 × 67 = 703.5 (round to 704)
 - d. The outdoor design temperature
 - d. 68°F
 - b. 18°C (64°F)
 - d. Transmission
 - b. Infiltration
 - a. 0.04
Outside air film = 0.17;
4″ brick = 0.44; ½″ plywood sheathing = 0.63;
FG insulation = 3.72 × 5.5″ = 20.46;
vapour barrier = 0; ½″ GWB = 0.45;
inside air film = 0.68
Aggregate “R” value = 22.83 “U” value = 1 ÷ 22.83 = 0.04 - d. Low “E” – argon-filled
 - c. Thermal bridging
 - b. 1,930 BTUH(20 × 15 × 8) ft³ × (2/3 ACH × 0.018) × (72 – 5) = 2400 × 0.012 × 67 = 1,930 BTUH
 - c. The rate would double
 - a. The rate would be halved
 - d. The ODT for the two houses will be different.
 - c. 1 ACH
 - b. 0.06
 - a. 15.0(3 × 5.0/inch)
 - a. 1/3 ACH
 - c. 22°F
 - Windows: (2) × 3′ × 5′ × 0.59 × (72 – -16) = 1,558 BTUH
Net walls: ((11 × 8) + (12 × 8)) – 30 = 154 ft²
154 × 0.05 × 88 = 678 BTUH
Ceiling: (12′ × 11′) × 0.03 × 88 = 348 BTUH
Floor: (12′ × 11′) × 0.05 × 88 = 581 BTUH
Infiltration: (12′ × 11′ × 8′) × (2/3 × 0.018) × 88 = 1,115 BTUH
Total heat loss: 4,280 BTUH - a. 1,164 BTUH(17.5′ × 33.25′) × 0.04 × (65 – 15) = 1,164 BTUH
 
Competency F2
Self Test 2
- a. PeX “A”
 - d. all varieties need oxygen-barrier, whether in wet or dry systems
 - c. 2 ½″ polystyrene
 - a. in the ceiling below
 - a. to give the wall more stability
 - c. a heat exchanger
 - b. dry systems
 - a. reflective foil
 - b. they operate at low temperatures is a false statement
 - c. make a first pass 6 inches from the outside walls, then turn 180° with another 6-inch pass, then resume normal loop layout
 - b. 9″ o.c. from Table (2.2A?)
 - c. 40 btuh/ft²
 - b. 300 feet is the norm although there may be some manufacturers who differ
 - d. 200 ft² – 84.5 ft² = 115.5 ft² of available area. 3050 btuh ÷ 115.5 ft² = 26.41 btuh/ft² of floor output. From Table (2.2A?), this is 9″ o.c. tube spacing. 115.5 × 1.3 (tube spacing factor for 9″ o.c.) = 150 feet of tubing
 - b. infra-red thermometer
 - c. 2:1
 - b. 100 psi for 30 minutes
 - b. its output
 - a. the single circuit with the highest head loss served by the pump
 - c. flow rate and feet of head
 - b. #4
 - a. 19.2 GPM 48,000 ÷ (5 × 60 × 8.33)
 - d. 12,000 12 inches × 1,000 millinches/inch
 - d. 9 feet of head 180 measured feet × 1.5 (fitting allowance) = 270 equivalent feet. Under the 400 millinch column, 270 equivalent feet = 9 ft. head
 - c. globe
 - a. reset control
 - c. hydraulic separation
 - b. its inner plate surface area
 - c. 3.12 feet of head              37,000 btuh ÷ 10,000 btuh/USGPM = 3.7 GPM
(3.7 ÷ 3.2)² = 1.156 1.156² = 1.3369 psi
1.3369 psi × 2.31 ft hd/psi = 3.088 (3.09) feet head - c. a differential bypass valve
 - a. flow rate
 - a. 17.56 29 feet × .433 psi/ft = 12.56 12.56 + 5 = 17.56 psi
 - c. 2.02 USG (45,000 ÷ 59,500) × 2 gal = 1.51 USG 1.51 × 1.34 (temp. adj.) = 2.02
 - a. boiler operation
 - c. 1 ¼″ 65,000 BTUH on Table 2.8 = 1 ¼″ pipe
 
Competency F3
Self Test 3
- d. a pole
 - c. a throw
 - a. by their number of poles and throws
 - c. a momentary switch
 - b. open on rise
 - d. aquastats
 - c. a pressure switch
 - d. an end switch
 - b. 24V AC
 - b. 24V AC
 - b. the hot leg
 - d. EMR
 - b. 24V AC
 - d. 120V AC
 - c. when the coil is energized, the contact positions will reverse
 - d. a SPDT switch
 - b. a low water cutoff
 - c. a DPDT switch
 - c. a pressure switch
 - d. an SSR
 
Competency F4
Self Test 4
- d. lowering the aquastat setting on a non-condensing boiler
 - b. a secondary heat exchanger
 - c. hydraulic separation
 - c. 4 diameters apart
 - c. 10,000 8.33 lbs/USG x 60 min/hr x 20°FΔT
 - a. an end switch
 - b. cold start
 - d. the lines that represent wires won’t cross each other
 - c. on the face of the transformer
 - a. “C”
 - b. “R”
 - d. “Y” and “W”
 - a. at the mixing point
 - b. in the boiler return piping
 - c. a diverting valve has less head loss than a mixing valve
 - a. it needs a remote sensor
 - b. 1 inlet and 2 outlets
 - d. a 4-way mixing valve
 - c. outdoor reset
 - c (design supply temp – room temp) ÷ (room temp – outdoor design temp)
 - a. warm weather shutdown point (WWSD)
 - d. a cooling thermostat
 - a. a DPDT switch
 - a. a normally closed relay contact
 - c. the zone valve opens
 - c. the pump turns on and the burner fires
 - a. 140°F
 - d. 2 N.O. contacts
 - a. loads
 - a. in series, in the burner circuit
 - d. 20
 - b. near the draft hood
 - c. a hot water tank
 - c. 2.50 60VA ÷ 24VAC = 2.50A
 - b. only the extra thermostats and zone valve motors
 - c. the DHW zone valve
 - d. none
 - b. in parallel
 - a. in series
 - a. 1
 - b. make sure the circuit isn’t powered
 - d. turn the adjusting screw so that the pointer is directly over “0”
 
Competency F5
Self Test 5
- b. wiring that is not factory installed
 - c. cable consists of individual wires
 - a. to prevent abrasion of the wire insulation
 - d. Canadian Electrical Code
 - a. metal
 - a. gang-able
 - d. through knockouts on the box wall
 - a. 1.5 m
 - b. “Teck” is waterproof; “BX” isn’t
 - b. a threaded adapter
 - d. galvanized Schedule 40 pipe
 - c. a raceway
 - d. 100 Watts
 - a. maintain at least 2 inches physical distance between them
 - b. solderless-type
 - c. [latex]\dfrac{5}{8}[/latex]″ – ¾″
 - d. a terminal strip
 - b. ¼″ – [latex]\dfrac{3}{8}[/latex]″
 - d. two bonding wires
 - b. a heat sink